Appendix d - vcc-x bacnet, Vcc-x bacnet, Parameters – Orion System VCC-X Controller User Manual
Page 105: Vcc-x controller technical guide
VCC-X Controller Technical Guide
APPENDIX D - VCC-X BACnet
®
105
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Compressor
D2 Alarm
BI:60
Compressor D2 High
Pressure Alarm. Stops
Compressor.
Outside Coil
'D' Temp
Switch
BI:61
Outside Coil 'D' Temp
Switch for Defrost Mode
Module #4
Binary Input
#4
BI:62
Future use for Binary Input
#4
On Board
Relay 1
BI:63
Current Status of Main Fan
Relay #1 on Main Board
On Board
Relay 2
BI:64
Current Status of
Confi gurable Relay #2 on
Main Board
On Board
Relay 3
BI:65
Current Status of
Confi gurable Relay #3 on
Main Board
On Board
Relay 4
BI:66
Current Status of
Confi gurable Relay #4 on
Main Board
On Board
Relay 5
BI:67
Current Status of
Confi gurable Relay #5 on
Main Board
On Board
Relay 6
BI:68
Current Status of
Confi gurable Relay #6 on
Main Board
On Board
Relay 7
BI:69
Current Status of
Confi gurable Relay #7 on
Main Board
On Board
Relay 8
BI:70
Current Status of
Confi gurable Relay #8 on
Main Board
Expansion
Module Relay
1
BI:71
Current Status of
Confi gurable Relay #1 on
EM1 Board
Expansion
Module Relay
2
BI:72
Current Status of
Confi gurable Relay #2 on
EM1 Board
Expansion
Module Relay
3
BI:73
Current Status of
Confi gurable Relay #3 on
EM1 Board
Expansion
Module Relay
4
BI:74
Current Status of
Confi gurable Relay #4 on
EM1 Board
Expansion
Module Relay
5
BI:75
Current Status of
Confi gurable Relay #5 on
EM1 Board
12 Relay
Expansion
Relay 1
BI:76
Current Status of
Confi gurable Relay #1 on
12 Relay Board
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
12 Relay
Expansion
Relay 2
BI:77
Current Status of
Confi gurable Relay #2 on
12 Relay Board
12 Relay
Expansion
Relay 3
BI:78
Current Status of
Confi gurable Relay #3 on
12 Relay Board
12 Relay
Expansion
Relay 4
BI:79
Current Status of
Confi gurable Relay #4 on
12 Relay Board
12 Relay
Expansion
Relay 5
BI:80
Current Status of
Confi gurable Relay #5 on
12 Relay Board
12 Relay
Expansion
Relay 6
BI:81
Current Status of
Confi gurable Relay #6 on
12 Relay Board
12 Relay
Expansion
Relay 7
BI:82
Current Status of
Confi gurable Relay #7 on
12 Relay Board
12 Relay
Expansion
Relay 8
BI:83
Current Status of
Confi gurable Relay #8 on
12 Relay Board
12 Relay
Expansion
Relay 9
BI:84
Current Status of
Confi gurable Relay #9 on
12 Relay Board
12 Relay
Expansion
Relay 10
BI:85
Current Status of
Confi gurable Relay #10 on
12 Relay Board
12 Relay
Expansion
Relay 11
BI:86
Current Status of
Confi gurable Relay #11 on
12 Relay Board
12 Relay
Expansion
Relay 12
BI:87
Current Status of
Confi gurable Relay #12 on
12 Relay Board
Refrig Module
#1 Relay #1
BI:88
Current Status of
Compressor A1 Enable
Refrig Module
#1 Relay #2
BI:89
Current Status of
Compressor A2 Enable
Refrig Module
#1 Relay #3
BI:90
Current Status of A1/A2
Condenser Enable
Refrig Module
#1 Relay #4
BI:91
Current Status of A1/A2
Reversing Valve
Refrig Module
#2 Relay #1
BI:92
Current Status of
Compressor B1 Enable
Refrig Module
#2 Relay #2
BI:93
Current Status of
Compressor B2 Enable
Refrig Module
#2 Relay #3
BI:94
Current Status of B1/B2
Condenser Enable
Refrig Module
#2 Relay #4
BI:95
Current Status of B1/B2
Reversing Valve
Refrig Module
#3 Relay #1
BI:96
Current Status of
Compressor C1 Enable
Refrig Module
#3 Relay #2
BI:97
Current Status of
Compressor C2 Enable
Refrig Module
#3 Relay #3
BI:98
Current Status of C1/C2
Condenser Enable
VCC-X BACnet
®
Parameters