Page 21: Vcc-x controller outputs, Figure 7: vcc-x controller output wiring

background image

VCC-X Controller Technical Guide

VCC-X CONTROLLER WIRING

21

VCC-X Controller Output Wiring

Figure 7: VCC-X Controller Output Wiring

NOTE:

ALL RELAY OUTPUTS ARE NORMALLY

OPEN AND RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

CONFIGURABLE RELAY OUTPUT #5

CONFIGURABLE RELAY OUTPUT #4

CONFIGURABLE RELAY OUTPUT #3

CONFIGURABLE RELAY OUTPUT #2

24 VAC POWER

SUPPLY FAN

24 VAC ONLY

R1

G

R4
R5

R3

R2

H

V

A

C

U

N

IT

C

O

NNECTIO

NS

R

COMM

CONFIGURABLE RELAY OUTPUT #6

R6

AOUT1
AOUT2
AOUT3

GND
GND

24VAC

GND

VCC-X CONTROLLER

Line
Voltage

Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA

R7
R8

CONFIGURABLE RELAY OUTPUT #7
CONFIGURABLE RELAY OUTPUT #8

AOUT4

ECONOMIZER

ACTUATOR

SUPPLY FAN VFD

+

COM

2 +

Y1

3

COM

1

MODULATING HEATING

(SCR OR HOT WATER VALVE)

+

COM

EXHAUST FAN VFD

+

COM

SHIELD

SHIELD

5 Economizer Feedback

NOTE: RELAY CONTACTS R2-R8 MAY BE CONFIGURED FOR:

1.) COOLING STAGES
2.) HEATING STAGES

4.) EMERGENCY HEAT
5.) MOD HEAT ENABLE
6.) MOD COOL ENABLE
7.) MORNING WARM-UP

9.)

11.) LOW AMBIENT
12.) EXHAUST
13.)

ECONOMIZER

14.)

15.) OCCUPIED
16.) OVERRIDE

10.) PREHEAT

3.) AUX HEAT

17.) ALARM

REHEAT

HEAT WHEEL

8.) MORNING COOL-DOWN

VCC-X Controller Outputs

The VCC-X Controller must be connected to 24 VAC as shown
in the wiring diagram below. Please see Table 1 for correct VA
requirements to use when sizing the transformer(s) used for powering
the Controller.

Also please note that when wiring the VCC-X Controller, its contacts
must be wired as wet contacts (connected to 24 VAC).