Vcc-x controller wiring, Vcc-x controller input wiring, Vcc-x controller technical guide 20 – Orion System VCC-X Controller User Manual
Page 20: Vcc-x controller inputs, Zone, Figure 6: vcc-x controller input wiring, 24vac gnd

Zone
Zone
VCC-X CONTROLLER WIRING
VCC-X Controller Technical Guide
20
VCC-X Controller Input Wiring
Figure 6: VCC-X Controller Input Wiring
SPACE
TEMPERATURE SENSOR
OUTDOOR AIR
TEMPERATURE SENSOR
L
L
R
R
E
E
NORMAL
NORMAL
OVR
OVR
O
O
O
O
C
C
R
R
M
M
E
E
R
R
A
A
W
W
AUX
GND
TEMP
SUPPLY AIR TEMP. SENSOR
AI1
AI2
AI3
AI4
AI5
GND
GND
EMERGENCY SHUTDOWN SWITCH
PROOF OF FLOW SWITCH
DIRTY FILTER SWITCH
REMOTE FORCED DEHUMIDIFICATION
BIN1
BIN2
BIN3
BIN4
COM
COM
24VAC
GND
VCC-X CONTROLLER
Line Voltage
Size Transformer For
Correct Total Load.
VCC-X Controller = 15 VA
HOOD ON/OFF
REMOTE FORCED OCCUPIED
REMOTE FORCED COOLING
REMOTE FORCED HEATING
COM
COM
BIN5
BIN6
BIN7
BIN8
RETURN AIR TEMP. SENSOR
OE258-01 BUILDING STATIC
PRESSURE SENSOR
+
LO
W
HIG
H
COM
OUT
EXC
+
+
PLASTIC TUBING
TO BUILDING
PRESSURE
SENSING
LOCATIONS
AI6
AI7
+
-
REMOTE SUPPLY AIR
TEMPERATURE RESET SIGNAL
(CONFIGURABLE 0-10VDC)
(BY OTHERS)
CONNECT FRP TUBING TO HIGH PRESSURE
PORT (BOTTOM TUBE) AND ROUTE TO STATIC
PRESSURE PICKUP PROBE LOCATED IN UNIT
DISCHARGE. LEAVE PORT MARKED “LO” OPEN
TO ATMOSPHERE
OE271
STATIC PRESSURE
TRANSDUCER
SPLICE IF REQUIRED
(SEE DETAILED
WIRING DIAGRAM)
MOUNT IN HVAC UNIT
RETURN AIR STREAM
MOUNT IN HVAC UNIT
SUPPLY AIR STREAM
PLUG INTO VCC-X
CONTROLLER’S
PHONE JACK
NOTE: EITHER A FLUSH MOUNT
ROOM SENSOR OR A DIGITAL
E-BUS ROOM SENSOR
MAY BE USED.
VCC-X Controller Inputs
The VCC-X Controller is designed with 8 analog inputs, 4 analog
outputs, 8 binary inputs and 8 relay outputs.
There are also 2 E-BUS Expansion Ports which allow the use of
communicating sensors and the E-BUS Modules.
See Figures 6 & 7 for wiring details. Detailed wiring for all inputs
and outputs are found on the pages that follow.