APPENDIX D - VCC-X BACnet

®

VCC-X Controller Technical Guide

100

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Morning

Warmup /

Morning

Cool-Down

AV:16

If Morning Warm-Up or

Morning Cool-Down is

confi gured then upon

entering the occupied mode,

the Warm-Up Mode will

be activated if the return air

is below this temperature

by one degree. If the return

air is above this temperature

by one degree, the

Cool-Down Mode will be

activated.

50

90

Warm-Up

SAT Heating

Setpoint

AV:17

During Morning Warm-Up,

the Supply Air Temperature

will be controlled to this

Setpoint.

40

240

Cool-Down

SAT Cooling

Setpoint

AV:18

During Morning Cool-

Down, the Supply Air

Temperature will be

controlled to this Setpoint.

30

80

Mechanical

Cooling

Outdoor Air

Lockout

AV:19

Mechanical Cooling will

be locked out when the

Outdoor Air Temperature is

below this Setpoint.

-30

100

Mechanical

Heating

Outdoor Air

Lockout

AV:20

Mechanical Heating will

be locked out when the

Outdoor Air Temperature is

above this Setpoint.

-30

150

Low

Supply Air

Temperature

Cutoff

AV:21

Cooling will be disabled if

the Supply Air Temperature

falls below this value. See
sequence for more details.

0

100

High

Supply Air

Temperature

Cutoff

AV:22

Heating will be disabled if

the Supply Air Temperature

rises above this value. See
sequence for more details.

0

250

Preheater

Cool Mode

Leaving SP

AV:23

If the Preheater is enabled,

and the unit is in the

Cooling Mode, this setpoint

will be sent to the

Preheat-X Controller to

control Leaving Air

Temperature.

35

90

Preheater Vent
Mode Leaving

SP

AV:24

If the Preheater is enabled,

and the unit is in the

Vent Mode, this setpoint

will be sent to the

Preheat-X Controller to

control Leaving Air

Temperature.

35

90

Preheater Heat
Mode Leaving

SP

AV:25

If the Preheater is enabled,

and the unit is in the

Heating Mode, this setpoint

will be sent to the

Preheat-X Controller to

control Leaving Air

Temperature.

35

90

BACnet

®

Properties for the VCC-X Controller

Parameter

Object

Description

Limits

Outdoor Air

Dewpoint

Setpoint

AV:26

On an MUA unit, if the OA

dewpoint rises above this

setpoint, Dehumidifi cation

is initiated.

35

80

Economizer

Enable

Setpoint

AV:27

The economizer is enabled

if the outdoor drybulb,

dewpoint, or wetbulb

temperature falls below this

setpoint.

-30

80

Heat Wheel
Defrost En-

able

Setpoint

AV:28

The unit will go into

Heat Wheel Defrost if the

Outdoor Air is below this

setpoint.

0

50

Preheat

Setpoint

AV:29

If the Supply Fan is
energized this is the

temperature at which the

Preheat Relay will activate

or the Preheat-X Controller
will activate. Operates only

in the Occupied Mode.

-30

70

Maximum

Sensor Slide

Adjust

AV:30

If your space sensor has the

optional slide adjustment

feature, this is the maximum

amount the slide can adjust

the current heating and
cooling setpoints up or

down with full defl ection of

the slide.

0

10

Space

Sensor

Calibration

Offset

AV:31

If the Space Temperature

Sensor is reading

incorrectly, you can use this

option to enter an offset

temperature to adjust the

Sensor’s Temperature.

-100

100

Supply Air

Sensor

Calibration

Offset

AV:32

If the Supply Air

Temperature Sensor is

reading incorrectly, you can

use this option to enter an

offset temperature to adjust

the Sensor’s Temperature.

-100

100

Return Air

Sensor

Calibration

Offset

AV: 33

If the Return

Temperature Sensor is

reading incorrectly, you can

use this option to enter an

offset temperature to adjust

the Sensor’s Temperature.

-100

100

Outdoor Air

Sensor

Calibration

Offset

AV: 34

If the Outdoor Temperature

Sensor is reading

incorrectly, you can use this

option to enter an offset

temperature to adjust the

Sensor’s Temperature.

-100

100

CO2 Sensor

Calibration

Offset

AV:35

If the CO

2

Sensor is reading

incorrectly, you can use this

option to enter an offset

value to adjust the Sensor’s

CO

2

reading.

-500

500