APPENDIX D - VCC-X BACnet
®
VCC-X Controller Technical Guide
104
VCC-X BACnet
®
Parameters
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Bad or
Missing
Module #1
BI:38
Refrigeration Module #1 is
bad or missing.
Bad or
Missing
Module #2
BI:39
Refrigeration Module #2 is
bad or missing.
Bad or
Missing
Module #3
BI:40
Refrigeration Module #3 is
bad or missing.
Bad or
Missing
Module #4
BI:41
Refrigeration Module #4 is
bad or missing.
Bad or
Missing
Preheat
Module
BI:42
Preheater Module is bad or
missing.
Bad or
Missing
Reheat Board
BI: 43
The MHGR board is
confi gured but not detected.
Bad or
Missing
MODGAS
Board
BI: 44
The MODGAS board is
confi gured but not detected.
Bad or Miss-
ing EM1
Module
BI:45
EM1 Expansion Board is
bad or missing.
Bad or
Missing 12
Relay
Expansion
Board.
BI: 46
The 12 Relay Expansion
Board is confi gured but not
detected.
Compressor
A1 Safety
BI:47
Compressor A1 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Compressor
A2 Safety
BI:48
Compressor A2 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Outside Coil
'A' Temp
Switch
BI:49
Outside Coil 'A' Temp
Switch for Defrost Mode
Module #1
Binary Input
#4
BI:50
Future use for Binary Input
#4
BACnet
®
Properties for the VCC-X Controller
Parameter
Object
Description
Limits
Compressor
B1 Alarm
BI:51
Compressor B1 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Compressor
B2 Alarm
BI:52
Compressor B2 Not
Running. This RSM alarm
occurs when a compressor
relay is on, but there is not
24VAC at the Comp Status
input for the compressor.
Outside Coil
'B' Temp
Switch
BI:53
Outside Coil 'B' Temp Switch
for Defrost Mode
Module #2
Binary Input
#4
BI:54
Future use for Binary Input
#4
Compressor
C1 Alarm
BI:55
Compressor C1 High
Pressure Alarm. Stops
Compressor.
Compressor
C2 Alarm
BI:56
Compressor C2 High
Pressure Alarm. Stops
Compressor.
Outside Coil
'C' Temp
Switch
BI:57
Outside Coil 'C' Temp
Switch for Defrost Mode
Module #3
Binary Input
#4
BI:58
Future use for Binary Input
#4
Compressor
D1 Alarm
BI:59
Compressor D1 High
Pressure Alarm. Stops
Compressor.