Appendix d - vcc-x bacnet, Bacnet, Pics – Orion System VCC-X Controller User Manual
Page 108: Vcc-x controller technical guide 108, Protocol implementation conformance statement

APPENDIX D - VCC-X BACnet
®
VCC-X Controller Technical Guide
108
BACnet
®
PICS
BACnet
®
Protocol Implementation Conformance Statement
Vendor
Listing Status
WattMaster Controls, Inc.
8500 NW River Park Drive, Suite 108A
Parkville, MO 64152
USA
Listed Product
Test Requirements
BACnet
®
Protocol Revision
Date Tested
Requirements as of December 2011
Revision 12 (135-2010)
April 2013
Product Name
Model Number
Software Version
VCC-X Controller
OE335-26B-VCBX
2.13
BACnet
®
Standardized Device Profi le (Annex L)
BACnet Application Specifi c Controller (B-ASC)
BIBBs Supported
Data Sharing
ReadProperty-B
DS-RP-B
ReadPropertyMultiple-B
DS-RPM-B
WriteProperty-B
DS-WP-B
Device and Network Management
Dynamic Device Binding-B
DM-DDB-B
Dynamic Object Binding-B
DM-DOB-B
DeviceCommunication Control-B
DM-DCC-B
Object Type Support
Device
Analog Input
Analog Value
Binary Input
Binary Value
Device does not support CreateObject, DeleteObject, and there are no Proprietary Properties.
Data Link Layer Options
Media
Options
MS/TP Master
9600,19200, 38400, 57600, 76800
Character Set Support
ANSI X3.4