Vcc-x expansion module 1 wiring, Vcc-x em1 expansion module output wiring, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual
Page 41: 41 vcc-x em1 expansion module outputs, Vcc-x em1 expansion module, Line voltage, Economizer 14.)
VCC-X Controller Technical Guide
VCC-X EXPANSION MODULE 1 WIRING
41
VCC-X EM1 Expansion Module Outputs
The VCC-X EM1 Expansion Module must be connected to 24
VAC as shown in the wiring diagram below. Please see Table 1 for
correct VA requirements to use when sizing the transformer(s) used
for powering the expansion module.
Also, please note that when wiring the VCC-X EM1 Expansion
Module, its contacts must be wired as wet contacts (connected to
24 VAC).
See Figure 26 below for input wiring.
VCC-X EM1 Expansion Module Output Wiring
Figure 26: VCC-X EM1 Expansion Module Output Wiring Diagram
NOTE:
ALL RELAY OUTPUTS ARE NORMALLY
OPEN AND RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD
CONFIGURABLE RELAY OUTPUT #3
CONFIGURABLE RELAY OUTPUT #2
CONFIGURABLE RELAY OUTPUT #1
24 VAC ONLY
R1
R4
R5
R3
R2
HV
AC
U
N
IT
CO
NN
EC
T
ION
S
24 VAC POWER
RC
R
CONFIGURABLE RELAY OUTPUT #4
CONFIGURABLE RELAY OUTPUT #5
CHILLED WATER VALVE ACTUATOR
2 +
Y1
3
COM
1
VCC-X EM1
Expansion Module
WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Modules must be wired in such a way that the expansion
modules and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.
AOUT1
AOUT2
24VAC
GND
Line Voltage
Size Transformer For
Correct Total Load.
VCC-X E 1 Module = 5 VA
M
GND
AOUT3
RETURN AIR
DAMPER ACTUATOR
2 +
Y1
3
COM
1
RETURN AIR BYPASS
DAMPER ACTUATOR
2 +
Y1
3
COM
1
Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions.
WattMaster Label
#L102196-A
Rev.: 1A
B
+24
VAC
GND
RELA
Y
C
ONT
A
CT
RA
TING
IS
1
A
MP
MAX
@
24
V
A
C
R1
R2
R3
R4
R5
RC
RELAY OUTPUT
TERMINALS
ANALOG OUTPUT TERMINALS
GND
RETURN DAMPER
RETURN BYPASS
CHILLED WATER
AOUT4
PWM –
PWM +
E-BUS
CONNECT
24 VAC POWER ONLY
WARNING! POLARITY
MUST BE OBSERVED OR
THE CONTROLLER WILL
BE DAMAGED
POWER INPUT TERMINAL BLOCK
PUT
T
VCC-X Expansion Module 1
Orion No.: OE336-23-VCCXEM1
AAON No.: V53990
NOTE: RELAY CONTACTS R1-R5 MAY BE CONFIGURED FOR:
1.) COOLING STAGES
2.) HEATING STAGES
4.) EMERGENCY HEAT
5.) MOD HEAT ENABLE
6.) MOD COOL ENABLE
7.) MORNING WARM-UP
9.)
11.) LOW AMBIENT
12.) EXHAUST
13.)
ECONOMIZER
14.)
15.) OCCUPIED
16.) OVERRIDE
10.) PREHEAT
3.) AUX HEAT
17.) ALARM
REHEAT
HEAT WHEEL
8.) MORNING COOL-DOWN