VCC-X EXPANSION MODULE 1 WIRING

41

VCC-X EM1 Expansion Module Outputs

The VCC-X EM1 Expansion Module must be connected to 24
VAC as shown in the wiring diagram below. Please see Table 1 for
correct VA requirements to use when sizing the transformer(s) used
for powering the expansion module.

Also, please note that when wiring the VCC-X EM1 Expansion
Module, its contacts must be wired as wet contacts (connected to
24 VAC).

See Figure 26 below for input wiring.

VCC-X EM1 Expansion Module Output Wiring

Figure 26: VCC-X EM1 Expansion Module Output Wiring Diagram

NOTE:

ALL RELAY OUTPUTS ARE NORMALLY

OPEN AND RATED FOR 24 VAC POWER
ONLY - 1 AMP MAXIMUM LOAD

CONFIGURABLE RELAY OUTPUT #3

CONFIGURABLE RELAY OUTPUT #2

CONFIGURABLE RELAY OUTPUT #1

24 VAC ONLY

R1

R4

R5

R3

R2

HV

AC

U

N

IT

CO

NN

EC

T

ION

S

24 VAC POWER

RC

R

CONFIGURABLE RELAY OUTPUT #4

CONFIGURABLE RELAY OUTPUT #5

CHILLED WATER VALVE ACTUATOR

2 +

Y1

3

COM

1

VCC-X EM1
Expansion Module

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Modules must be wired in such a way that the expansion
modules and the controller are always powered together. Loss of power to the
expansion module will cause the controller to become inoperative until power is
restored to the expansion module.

AOUT1

AOUT2

24VAC

GND

Line Voltage

Size Transformer For
Correct Total Load.
VCC-X E 1 Module = 5 VA

M

GND

AOUT3

RETURN AIR

DAMPER ACTUATOR

2 +

Y1

3

COM

1

RETURN AIR BYPASS

DAMPER ACTUATOR

2 +

Y1

3

COM

1

Belimo Actuator Wiring
Shown. Consult Factory
For Other Manufacturer
Wiring Instructions.

WattMaster Label

#L102196-A

Rev.: 1A

B

+24

VAC

GND

RELA

Y

C

ONT

A

CT

RA

TING

IS

1

A

MP

MAX

@

24

V

A

C

R1

R2

R3

R4

R5

RC

RELAY OUTPUT

TERMINALS

ANALOG OUTPUT TERMINALS

GND

RETURN DAMPER

RETURN BYPASS

CHILLED WATER

AOUT4

PWM –

PWM +

E-BUS

CONNECT

24 VAC POWER ONLY

WARNING! POLARITY

MUST BE OBSERVED OR

THE CONTROLLER WILL

BE DAMAGED

POWER INPUT TERMINAL BLOCK

PUT

T

VCC-X Expansion Module 1

Orion No.: OE336-23-VCCXEM1

AAON No.: V53990

NOTE: RELAY CONTACTS R1-R5 MAY BE CONFIGURED FOR:

1.) COOLING STAGES
2.) HEATING STAGES

4.) EMERGENCY HEAT
5.) MOD HEAT ENABLE
6.) MOD COOL ENABLE
7.) MORNING WARM-UP

9.)

11.) LOW AMBIENT
12.) EXHAUST
13.)

ECONOMIZER

14.)

15.) OCCUPIED
16.) OVERRIDE

10.) PREHEAT

3.) AUX HEAT

17.) ALARM

REHEAT

HEAT WHEEL

8.) MORNING COOL-DOWN