Appendix b - vcc-x lcd screens, Main screens map and settings screens, Vcc-x controller technical guide – Orion System VCC-X Controller User Manual
Page 83: Main screens map, Settings screens
VCC-X Controller Technical Guide
APPENDIX B - VCC-X LCD SCREENS
83
Main Screens Map and Settings Screens
Main Screens Map
Refer to the following map when navigating through the LCD Main
Screens. The fi rst screen is an initialization screen. To scroll through
the rest of the screens, press the
button.
VCCX AHU
VER X.XX
Output
Override
Status
Settings
Alarms or
No Alarms
Press to scroll through the Output Override Screens.
Press to scroll through the Alarm Screens.
Press to go to the Alarm Screens.
Press to go to Output Override Screens.
Press to scroll through Settings Screens.
Press to scroll through the Status Screens.
Press to go to the Settings Screens.
Press to go to the Status Screens.
Settings Screens
Refer to the following map when navigating through the Settings
Screens. From the Settings Screen, press
to scroll through
the screens.
Settings
MAC Addr
0 TO 254
ID Start
15000
BACnet
®
- CURRENT MAC ADDRESS
Valid range is 0 to 254. Default is 1.
BACnet
®
- CURRENT ID Start
ID #’s start in the 15000 block of numbers
and increment up or down by 1000.
Unit ID#
Addr #1-59
UNIT ADDRESS
Unit address. Valid range is 1-59. Default is 59.
485 Baud
Lo-Speed or
Hi-Speed
BAUD RATE SPEED
485 baud rate speed. Valid range is Lo-Speed or Hi-Speed.
Default is Hi-Speed.