Gasboy Enhanced Communications User Manual
Page 48

Serial-to-LAN Connection Installation
Page 48
MDE-4520C Enhanced Communications Installation Manual · February 2008
9
Close the terminal or Telnet session. Close the command prompt session if still open.
Disconnect the CAT-5 cross cable from the Test PC. If you are using the TCP/IP configuration
(refer to
.
10
Connect the CAT-5 cross cable to the second Serial to LAN adapter. Connect the modem cable
(9 to 25) to that Serial to LAN adapter.
Figure 35: Test PC to Gasboy System Connections through Two LAN Adapters
Gasboy System
C04532
Serial to
LAN Adapter
Serial to
LAN Adapter
Test PC
Q13850-C06
Q13240-09
CAT-5 Cross
Cable
SHM
C05618
Gasboy
Termination Box
Gasboy
D-Type
Connector
C05769
OR
OR
Serial Port
11
Using a terminal session (for example, HyperTerminal) with settings 9600, 8, N, 1, verify the
adapter is set up as described in
Settings for the Adapter Connected to a PC
on
(use
Direct Connect Mode for this test). Verify the IP address and port number are set to the values
supplied by the Network Administrator (or other IT personnel). If they are not supplied, use a
temporary value of IP address 192.168.1.102 and port 1001. Verify the remote IP address and
remote port number are set to match the values of the Gasboy system adapter. Also, verify the
baud rate matches the Gasboy system. Mark this adapter PC.
12
In the terminal session, click the disconnect button (If no disconnect button is available in your
terminal session, close the session). If necessary, change the baud rate to match the Gasboy
system (it may be necessary to close and re-open HyperTerminal for this change to take
affect). Click the connect button (If no connect button is available in your terminal session, re-
start the terminal session). Verify you can sign on to the Gasboy system and run system
commands. If unable to connect, ensure the adapter and Gasboy system are powered. Check
cable connection from the Gasboy system to the adapter, adapter to adapter, and the adapter to
PC. Check the system baud rate is set correctly for the port being used. It may be necessary to
default all the adapter settings and re-load them (refer to
on
section in this manual). If still unable to connect, try replacing the adapter. You must
be able to communicate with the Gasboy system at this level before going forward.
13
If you are using Direct Connect Mode, close the terminal session and skip to step
. If you are
using Modem Emulation Mode, repeat step
above (except follow the setting in Modem
Emulation Mode sub-section for this test). Ensure to load zeros for the remote IP address and
port number.