beautypg.com

Direct connect mode – Gasboy Enhanced Communications User Manual

Page 40

background image

Serial-to-LAN Connection Installation

Page 40

MDE-4520C Enhanced Communications Installation Manual · February 2008

Direct Connect Mode

For the Direct Connection mode, the following parameters must be set to the value listed for
the adapter connected to the PC. To view/edit the parameters below, enter “1” at the “Your
choice?” prompt and press ENTER.

Parameter
(

Figure 26

on

page 37

)

Value

Definition

Baud rate

Set to match the baud rate of the Gasboy system
port to which the adapter is connected

9600 is the default value

I/F Mode

4C

RS-232C, 8 bits, no parity, 1 stop bit

Flow

05

XON/OFF pass characters to host

Port

(see note below)

Range: 1 - 65535

Connect Mode

C5

Accept unconditional, auto start

Remote IP Adr

Set to IP address assigned to Gasboy system
adapter

IP address to link to at startup

(Remote) Port

Set to port assigned to Gasboy system adapter

Port to connect to when link is
established

Disconn Mode

C0

Disconnect with DTR drop, Telnet
mode

Flush Mode

44

Input buffer - clear at disconnect
Output buffer - clear at disconnect

Note: Every TCP connection is defined by a destination IP address and port number. For example, a Telnet

application commonly uses port number 23. A port number is similar to an extension on a PBX telephone
system. Range of port numbers available: 1 - 65535. Port numbers 0, 7, and 9999 are reserved and must not
be assigned to the adapter.

After the parameters have been changed, you can press ENTER at the “Your choice?” prompt
to display the current values. Remember to save the settings once they are set correctly (see

below).

Consult with your Network Administrator for changes to the IP address, gateway address,
subnet mask, or security changes. To change IP address, gateway address, subnet mask
parameters, enter “0” at the “Your choice?” prompt and then press ENTER. To change
security parameters, enter “6” at the “Your choice?” prompt and then press ENTER.

Once the parameters are set correctly, save the settings and exit setup by entering “9” at the
prompt and then press ENTER.