At the Gasboy System End
Note: The fueling position assembly must be mounted no lower than 18 inches above the
ground and no closer than 18 inches to any fuel dispenser.
Antenna Mast or Tower
• The height of the mast or tower will be determined by the line of sight requirement
between this antenna and the PC wireless antenna.
• You are allowed to use a 10-foot mast, or a 10-foot tower and 10-foot mast (11 feet to 18
feet total height), or a 20-foot 1 or 2 section tower and 10-foot mast (21 feet to 28 feet total
height) without the use of guy wires.
• If a tower base section is used, the manufacturers’ requirements for the installation of that
tower must be followed for the height of the tower installed.
Note: A tower and mast section is preferred as it encloses the wireless modem inside the
tower and protects it from being damaged.
Figure 4: Modem Inside the Tower
Modem Inside
the Tower
Gasboy System
(TopKAT)
Distance to the Modem Enclosure
For Gasboy systems other than a pedestal mount TopKAT unit, the modem enclosure must not
be more than 20 feet (6.1 meters) away. All other wire and conduit requirements specified in
the system installation manual must be followed.
Note: Do not use collar and conduit supplied with the kit.