4 index 6030 dpo inputs ch.4, 5 index 6040 log status – BECKHOFF EP9214-0023 User Manual
Page 98

Comissioning and Configuration
4.6.2.3.4
Index 6030 DPO Inputs Ch.4
Index
Name
Meaning
Data type
Flags
Default
6030:0
DPO Inputs Ch.4
Input of the first channel
UINT8
RO
0x18 (24
dec
)
6030:01
Error Us
The current monitoring of Us
has tripped. The bit must be re-
set by a Global Reset (F707:04)
or by the corresponding Reset
Us (7030:05). The output can-
not be activated as long as the
bit is set.
boolean
RO
0x00 (0
dec
)
6030:02
Error Up
The current monitoring of Up
has tripped. The bit must be re-
set by a Global Reset (F707:04)
or by the corresponding Reset
Us (7030:06). The output can-
not be activated as long as the
bit is set.
boolean
RO
0x00 (0
dec
)
6030:03
Warning Us
The monitoring has detected
overcurrent; the switching off of
output Us on this channel is im-
minent if the current consump-
tion of the branch does not de-
crease.
boolean
RO
0x00 (0
dec
)
6030:04
Warning Up
The monitoring has detected
overcurrent; the switching off of
output Us on this channel is im-
minent if the current consump-
tion of the branch does not de-
crease.
boolean
RO
0x00 (0
dec
)
6030:05
Status Us
0
bin
: The output is switched off
1
bin
: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6030:06
Status Up
0
bin
: The output is switched off
1
bin
: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6030:07
Channel Error
6030:01 or 6030:02 are set
boolean
RO
0x00 (0
dec
)
6030:08
Error Sum Current
Sum current oft he channel has
been exceeded. So the output
is switched off. An active reset
is required to set the output
again.
boolean
RO
0x00 (0
dec
)
6030:09
Warning Sum Current
An overcurrent peak has beenn
detected. If the output will be
loaded furtermore in this way it
will switch of.
boolean
RO
0x00 (0
dec
)
6030:0F
TxPDO State
boolean
RO
0x00 (0
dec
)
6030:10
TxPDO Toggle
boolean
RO
0x00 (0
dec
)
6030:11
Current Us
Current from Us
INT16
RO
0x0000 (0
dec
)
6030:12
Current Up
Current from Up
INT16
RO
0x0000 (0
dec
)
6030:13
Peak Value 1
Peak value of the 1. item, that
was measured for extended di-
agnosis of channel 4.
INT16
RO
0x0000 (0
dec
)
6030:14
Peak Value 2
Peak value of the 2. item, that
was measured for extended di-
agnosis of channel 4.
INT16
RO
0x0000 (0
dec
)
6030:17
Timestamp 1
Time stamp when the peak
value 6030:13 was measured
UINT64
RO
6030:18
Timestamp 2
Time stamp when the peak
value 6030:14 was measured
UINT64
RO
4.6.2.3.5
Index 6040 LOG Status
Index
Name
Meaning
Data type
Flags
Default
6040:0
LOG Status
UINT8
RO
0x12 (18
dec
)
6040:01
Logger Running
0: Logger still running
boolean
RO
0x00 (0
dec
)
6040:11
Elapsed Time
Time since the logger was
stopped
UINT32
RO
0x00000000 (0
dec
)
6040:12
Trigger Reason
Reason the logger was stopped
for
UINT16
RO
0x0000 (0
dec
)
EP9214-0023 and EP9224-0023
98
Version 2.0.0