Comissioning and Configuration
4.6.2.1.4
Index 8020 DPO Settings Ch.3
Index
Name
Meaning
Data type
Flags
Default
8020:0
DPO Set-
tings Ch.3
UINT8
RO
0x16 (22
dec
)
8020:02
Default
State Us
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8020:03
Default
State Up
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8020:04
Enable Sum
Current Lim-
itation
Sum current limitation:
0
bin
: disabled
1
bin
: enabled
boolean
RW
0x00 (0
dec
)
8020:11
Characteris-
tic
Specifies the characteristic with which the current
monitoring reacts:
0
dec
: very fast acting
1
dec
: fast acting
2
dec
: slow acting
3
dec
: time delay
UINT16
RW
0x0001 (1
dec
)
8020:12
Nominal
Current Us
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8020:13
Nominal
Current Up
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8020:14
Nominal
Sum Cur-
rent
Nominal total current
UINT16
RW
0x0FA0 (4000
dec
)
8020:15
Timestamp
1 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
8020:16
Timestamp
2 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
4.6.2.1.5
Index 8030 DPO Settings Ch.4
Index
Name
Meaning
Data type
Flags
Default
8030:0
DPO Set-
tings Ch.4
UINT8
RO
0x16 (22
dec
)
8030:02
Default
State Us
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8030:03
Default
State Up
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8030:04
Enable Sum
Current Lim-
itation
Sum current limitation:
0
bin
: disabled
1
bin
: enabled
boolean
RW
0x00 (0
dec
)
8030:11
Characteris-
tic
Specifies the characteristic with which the current
monitoring reacts:
0
dec
: very fast acting
1
dec
: fast acting
2
dec
: slow acting
3
dec
: time delay
UINT16
RW
0x0001 (1
dec
)
8030:12
Nominal
Current Us
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8030:13
Nominal
Current Up
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8030:14
Nominal
Sum Cur-
rent
Nominal total current
UINT16
RW
0x0FA0 (4000
dec
)
8030:15
Timestamp
1 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
8030:16
Timestamp
2 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)