4 technical data – BECKHOFF EP9214-0023 User Manual
Page 11

Product overview
Quick links
Installation
Configuration
UL requirements for UL approved modules
2.4
Technical data
Technical data
EP9214-0023
EP9224-0023
Rated voltage
24 V
DC
(-15 % / +20 %)
Power supply
Feed: Plug 7/8", max. 16 A for each Us/Up
Onward connection: Socket 7/8", max. 16 A for each Us/Up
Number of load outputs
4 x M8, for each Us and Up
Voltage drop V
ON
in the load
circuits
90 mV / Ampere
Parallel connection of several load
outputs
not permissible
Overload switch-off
dependent on selected load curve (20 ms at 3 x I
N
, see time/current
characteristics)
Temperature switch-off
Internal temperature switch-off
Switch-on delay
10, 100 or 200 ms (adjustable via CoE)
Selectivity
in case of an error, the channel concerned is switched off
Signalling contact
1
Reset contact
1
Connections for signal and reset
contacts
in : 1 x M8 plug
out : 1 x M8 socket
Fieldbus
EtherCAT
Fieldbus connection
2 x M8 sockets, screened, marked green
Electrical isolation
Control voltage/fieldbus: 500 V
Supply of the module circuitry
from the control voltage Us
Current consumption of the module
circuitry
typically 110 mA from Us,
typically 40 mA from Up
Process image
Inputs: 5 x 16 bit
Outputs: 5 x 16 bit
Inputs: 16 x 16 Bit
Outputs: 5 x 16 Bit
Data logging
-
40 samples ( 1 ms - 1000 ms
sample time)
Permissible ambient temperature
during operation
-25°C ... +60°C
Permissible ambient temperature
during storage
-25 °C... +85°C
Vibration / shock resistance
conforms to EN 60068-2-6 / EN 60068-2-27
EMC immunity/emission
conforms to EN 61000-6-2 / EN 61000-6-4
Dimensions
126 mm x 60 mm x 40 mm
Weight
approx. 450 g
Installation position
variable
Protection class
IP65, IP66, IP67 (according to EN 60529)
Approvals
CE, UL in preparation
EP9214-0023 and EP9224-0023
11
Version 2.0.0