2 index 6010 dpo inputs ch.2 – BECKHOFF EP9214-0023 User Manual
Page 96
![background image](https://www.manualsdir.com/files/774926/content/doc096.png)
Comissioning and Configuration
4.6.2.3.2
Index 6010 DPO Inputs Ch.2
Index
Name
Meaning
Data type
Flags
Default
6010:0
DPO Inputs Ch.2
Input of the first channel
UINT8
RO
0x18 (24
dec
)
6010:01
Error Us
The current monitoring of Us
has tripped. The bit must be re-
set by a Global Reset (F707:04)
or by the corresponding Reset
Us (7010:05). The output can-
not be activated as long as the
bit is set.
boolean
RO
0x00 (0
dec
)
6010:02
Error Up
The current monitoring of Up
has tripped. The bit must be re-
set by a Global Reset (F707:04)
or by the corresponding Reset
Us (7010:06). The output can-
not be activated as long as the
bit is set.
boolean
RO
0x00 (0
dec
)
6010:03
Warning Us
The monitoring has detected
overcurrent; the switching off of
output Us on this channel is im-
minent if the current consump-
tion of the branch does not de-
crease.
boolean
RO
0x00 (0
dec
)
6010:04
Warning Up
The monitoring has detected
overcurrent; the switching off of
output Us on this channel is im-
minent if the current consump-
tion of the branch does not de-
crease.
boolean
RO
0x00 (0
dec
)
6010:05
Status Us
0
bin
: The output is switched off
1
bin
: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6010:06
Status Up
0
bin
: The output is switched off
1
bin
: The output supplies 24 V
boolean
RO
0x00 (0
dec
)
6010:07
Channel Error
6010:01 or 6010:02 are set
boolean
RO
0x00 (0
dec
)
6010:08
Error Sum Current
Sum current oft he channel has
been exceeded. So the output
is switched off. An active reset
is required to set the output
again.
boolean
RO
0x00 (0
dec
)
6010:09
Warning Sum Current
An overcurrent peak has beenn
detected. If the output will be
loaded furtermore in this way it
will switch of.
boolean
RO
0x00 (0
dec
)
6010:0F
TxPDO State
boolean
RO
0x00 (0
dec
)
6010:10
TxPDO Toggle
boolean
RO
0x00 (0
dec
)
6010:11
Current Us
Current from Us
INT16
RO
0x0000 (0
dec
)
6010:12
Current Up
Current from Up
INT16
RO
0x0000 (0
dec
)
6010:13
Peak Value 1
Peak value of the 1. item, that
was measured for extended di-
agnosis of channel 2.
INT16
RO
0x0000 (0
dec
)
6010:14
Peak Value 2
Peak value of the 2. item, that
was measured for extended di-
agnosis of channel 2.
INT16
RO
0x0000 (0
dec
)
6010:17
Timestamp 1
Time stamp when the peak
value 6010:13 was measured
UINT64
RO
6010:18
Timestamp 2
Time stamp when the peak
value 6010:14 was measured
UINT64
RO
EP9214-0023 and EP9224-0023
96
Version 2.0.0