Comissioning and Configuration
4.6.2.1.2
Index 8000 DPO Settings Ch.1
Index
Name
Meaning
Data type
Flags
Default
8000:0
DPO Set-
tings Ch.1
UINT8
RO
0x16 (22
dec
)
8000:02
Default
State Us
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8000:03
Default
State Up
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8000:04
Enable Sum
Current Lim-
itation
Sum current limitation:
0
bin
: disabled
1
bin
: enabled
boolean
RW
0x00 (0
dec
)
8000:11
Characteris-
tic
Specifies the characteristic with which the current
monitoring reacts:
0
dec
: very fast acting
1
dec
: fast acting
2
dec
: slow acting
3
dec
: time delay
UINT16
RW
0x0001 (1
dec
)
8000:12
Nominal
Current Us
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8000:13
Nominal
Current Up
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8000:14
Nominal
Sum Cur-
rent
Nominal total current
UINT16
RW
0x0FA0 (4000
dec
)
8000:15
Timestamp
1 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
8000:16
Timestamp
2 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
4.6.2.1.3
Index 8010 DPO Settings Ch.2
Index
Name
Meaning
Data type
Flags
Default
8010:0
DPO Set-
tings Ch.2
UINT8
RO
0x16 (22
dec
)
8010:02
Default
State Us
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8010:03
Default
State Up
The output adopts this value if Enable Control via
Fieldbus (F707:01) is not set or no connection to the
fieldbus
boolean
RW
0x01 (1
dec
)
8010:04
Enable Sum
Current Lim-
itation
Sum current limitation:
0
bin
: disabled
1
bin
: enabled
boolean
RW
0x00 (0
dec
)
8010:11
Characteris-
tic
Specifies the characteristic with which the current
monitoring reacts:
0
dec
: very fast acting
1
dec
: fast acting
2
dec
: slow acting
3
dec
: time delay
UINT16
RW
0x0001 (1
dec
)
8010:12
Nominal
Current Us
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8010:13
Nominal
Current Up
Nominal current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8010:14
Nominal
Sum Cur-
rent
Nominal total current
UINT16
RW
0x0FA0 (4000
dec
)
8010:15
Timestamp
1 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
8010:16
Timestamp
2 Trigger
Trigger condition for extended diagnosis
UINT16
RW
0x0000 (0
dec
)
EP9214-0023 and EP9224-0023
76