9 index f80e dpo settings device – BECKHOFF EP9214-0023 User Manual
Page 81
![background image](https://www.manualsdir.com/files/774926/content/doc081.png)
Comissioning and Configuration
4.6.2.1.9
Index F80E DPO Settings Device
Index
Name
Meaning
Data type
Flags
Default
F80E:0
DPO Set-
tings Device
UINT8
RO
0x16 (22
dec
)
F80E:02
Enable Sum
Current Lim-
itation
Sum Current monitoring:
0
bin
: enabled
1
bin
: disabled
boolean
RW
0x00 (0
dec
)
F80E:03
Automatic
Restart Af-
ter Uncritic
Events on
Us
Switch on automatically after undervoltage und
overtemperature:
0
bin
: enabled
1
bin
: disabled
boolean
RW
0x00 (0
dec
)
F80E:04
Automatic
Restart Af-
ter Uncritic
Events on
Up
Switch on automatically after undervoltage und
overtemperature:
0
bin
: enabled
1
bin
: disabled
boolean
RW
0x00 (0
dec
)
F80E:11
Startup De-
lay
Sets the time that is kept between two switch-on pro-
cedures:
1
dec
: fast (10 ms)
2
dec
: moderate (100 ms)
3
dec
: slow (200 ms)
UINT16
RW
0x0001 (1
dec
)
F80E:12
Nominal
Sum Cur-
rent
Nominal sum current
INT16
RW
0x2710 (10000
dec
)
F80E:13
Sum Cur-
rent Charac-
teristic
Characteristic of sum current monitoring
UINT16
RW
0x0001 (1
dec
)
F80E:15
Timestamp
1 Trigger
Item that ist to be monitored for extended diagnosis:
0: Temperature Warning
1: Temperature Error
2: Us Warning
3: Us Error
4: Up Warning
5: Up Error
6: Global Error Bit
7: Sum Current Warning
8: Sum Current Error
16: Minmum Current Us
17: Maximum Current Us
18: Minimum Current Up
19: Maximum Current Up
20: Minimum Voltage Us
21: Maximum Voltage Us
22: Minimum Voltage Up
23: Maximum Voltage Up
25: Maximum Temperature
24: Minimum Temperature
UINT16
RW
0x0000 (0
dec
)
F80E:16
Timestamp
2 Trigger
Item that ist to be monitored for extended diagnosis:
0: Temperature Warning
1: Temperature Error
2: Us Warning
3: Us Error
4: Up Warning
5: Up Error
6: Global Error Bit
7: Sum Current Warning
8: Sum Current Error
16: Minmum Current Us
17: Maximum Current Us
18: Minimum Current Up
19: Maximum Current Up
20: Minimum Voltage Us
21: Maximum Voltage Us
22: Minimum Voltage Up
23: Maximum Voltage Up
25: Maximum Temperature
24: Minimum Temperature
UINT16
RW
0x0000 (0
dec
)
EP9214-0023 and EP9224-0023
81
Version 2.0.0