5 ep9214-0023, 1 ep9214-0023 - object description, 1 objects for parameterization – BECKHOFF EP9214-0023 User Manual
Page 45: 1 index 1011 restore default parameters, Parameterization, Ethercat xml device description

Comissioning and Configuration
4.5
EP9214-0023
4.5.1
EP9214-0023 - Object description
Note
Parameterization
Terminals' parameterization will be conducted by the CoE tab (double-click on the referring
object) or the Process data tab (PDO assignment)
Note
EtherCAT XML Device Description
The description correspond to the display of the CoE objects from the EtherCAT XML De-
vice Description. It is strongly recommended to download the latest revision of the corre-
sponding XML file from the Beckhoff website (http://www.beckhoff.com/english/default.htm?
download/elconfg.htm) and follow the installation instructions.
The CoE overview contains objects for different intended applications:
• Objects required for parameterization during commissioning
• Objects intended for regular operation e.g. through ADS access
• Objects for indicating internal settings (may be fixed)
• Further profile-specific objects indicating inputs, outputs and status information
The following section first describes the objects require for normal operation, followed by a complete
overview of missing objects.
4.5.1.1
Objects for parameterization
4.5.1.1.1
Index 1011 Restore default parameters
Index
Name
Meaning
Data
type
Flags
Default
1011:0
Restore
default
parameters
Making default settings
UINT8
RO
0x01 (1
dec
)
1011:01 SubIndex
001
If this object is set to "0x64616F6C" in the set
value dialog, all backup objects are reset to
their delivery state.
UINT32
RW
0x00000000
(0
dec
)
Index
Name
Meaning
Data type
Flags
Default
8000:0
DPO Settings
Ch.1
UINT8
RO
0x13 (19
dec
)
8000:02
Default State Us The output adopts this value if F707:01 is not set
boolean
RW
0x01 (1
dec
)
8000:03
Default State Up The output adopts this value if F707:01 is not set
boolean
RW
0x01 (1
dec
)
8000:11
Characteristic
Specifies the characteristic with which the current monitor-
ing reacts:
0
dec
: very fast acting
1
dec
: fast acting
2
dec
: slow acting
3
dec
: time delay
UINT16
RW
0x0001 (1
dec
)
8000:12
Nominal Current
Us
Nominal maximum current at the output
UINT16
RW
0x0FA0 (4000
dec
)
8000:13
Nominal Current
Up
Nominal maximum current at the output
UINT16
RW
0x0FA0 (4000
dec
)
EP9214-0023 and EP9224-0023
45
Version 2.0.0