Fig. 45: EP9214 - Status bits
Fig. 46: EP9214 - status bits
Initialization
When switching on the voltage supply to the EP9214/EP9224, all green LEDs and then all red LEDs are
switched on briefly to test the LEDs.
The LED is valid for both voltages and currents (Us and Up; OR).
LED
Status
Us / Up
Warning
Error
Us / Up
Description
Off
0
0
0
The output is ready
Green
1
0
0
The output is just switching on
Green
1
0
0
The output is switched on. Normal operating
status.
Flashing green
1
1
0
The output is still operating, but will switch off if
conditions remain unchanged (Warning Ux).
Flashing red
0
1
1
The output has been switched off. Switching on
again is not yet possible (waiting time of
20 seconds)
Red
0
0
1
The output has been deactivated and can be
returned to a normal state by a reset.
EP9214-0023 and EP9224-0023
44