6 conductor losses, 7 power outputs – BECKHOFF EP9214-0023 User Manual
Page 23

Mounting and cabling
Technical data
Technical data
Rated voltage according to IEC 61076-2-101
300 V (according to IEC 61076-2-101)
Contamination level according to IEC 60664-1
3/2 (according to IEC 60664-1)
Insulation resistance IEC 60512-2
>10
9
W
Current carrying capacity according to
IEC 60512-3
16 A at 40°C (according to IEC 60512-3)
Volume resistance according to IEC 60512-2
< 5 mW
Protection class conforms to IEC 60529
IP65/66/67, when screwed together
Permissible ambient temperature
-30°C to +80°C
Material properties
TPE-U (PUR) halogen-free according to DIN VDE 0472
Part 815,
flame-retardant according to cULus 20549
Approbations
UL
Cable outside diameter
7.80 ± 0.20 mm
Bending radius
min. 6 x D (external diameter)
Parameter
Max. speed 5 m/s, max. acceleration 10 m/s²
Number of cycles
At least 10 million cycles with a max. travel path of 20
meters
3.3.6
Conductor losses
In the case of the power cables ZK2030-xxxx-yyy, a total length of 15 m should not be exceeded at 16 A.
When wiring, note that with a rated voltage of 24 V the function of the modules can no longer be guaranteed
from a voltage drop of 6 V. Variations in the output voltage from the power supply unit must also be taken
into account.
Fig. 19: ZK2030-xxxx-yyy - Conductor losses
Alternatively, larger cable cross-section can be used, e.g. 2.5 mm
2
.
3.3.7
Power outputs
The supply voltages are output via four 4-pole M8 sockets in the lower third of the modules (1, 2, 3 and 4).
EP9214-0023 and EP9224-0023
23
Version 2.0.0