7 restoring the delivery state – BECKHOFF EP9214-0023 User Manual
Page 104
![background image](https://www.manualsdir.com/files/774926/content/doc104.png)
Comissioning and Configuration
4.7
Restoring the delivery state
Restoring the delivery state To restore the delivery state for backup objects in ELxxxx terminals, the CoE
object Restore default parameters, SubIndex 001 can be selected in the TwinCAT System Manager (Config
mode).
Fig. 65: Selecting the Restore default parameters PDO
Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the
value 0x64616F6C in field Hex and confirm with OK.
All backup objects are reset to the delivery state.
Fig. 66: Entering a restore value in the Set Value dialog
Note
Alternative restore value
In some older terminals the backup objects can be switched with an alternative restore
value:
Decimal value: 1819238756
Hexadecimal value: 0x6C6F6164
An incorrect entry for the restore value has no effect.
EP9214-0023 and EP9224-0023
104