Index
Name
Meaning
Data type
Flags
Default
1C33:0
SM input
parameter
Synchronization parameters for the inputs
UINT8
RO
0x20 (32
dec
)
1C33:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchronous with SM 3 event (no outputs
available)
• 2: DC - Synchronous with SYNC0 Event
• 3: DC - Synchronous with SYNC1 Event
• 34: Synchronous with SM 2 event (outputs
available)
UINT16
RW
0x0000 (0
dec
)
1C33:02
Cycle time
as 1C32:02
UINT32
RW
0x000F4240 (1000000
dec
)
1C33:03
Shift time
Time between SYNC0 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000384 (900
dec
)
1C33:04
Sync modes
supported
Supported synchronization modes:
• Bit 0: free run is supported
• Bit 1: synchronous with SM 2 event is
supported (outputs available)
• Bit 1: synchronous with SM 3 event is
supported (no outputs available)
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 01: input shift through local event
(outputs available)
• Bit 4-5 = 10: input shift with SYNC1 event (no
outputs available)
• Bit 14 = 1: dynamic times (measurement
through writing of 1C32:08 or 1C33:08)
UINT16
RO
0x0001 (1
dec
)
1C33:05
Minimum
cycle time
Minimum cycle time (in ns)
UINT32
RO
0x000F4240 (1000000
dec
)
1C33:06
Calc and
copy time
Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)
UINT32
RO
0x00000000 (0
dec
)
1C33:07
Minimum
delay time
UINT32
RO
0x00000384 (900
dec
)
1C33:08
Command
• 0: Measurement of the local cycle time is
stopped
• 1: Measurement of the local cycle time is
started
The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09,
1C33:03, 1C33:06, and 1C33:09 are updated with the
maximum measured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C33:09
Maximum
delay time
Time between SYNC1 event and reading of the in-
puts (in ns, only DC mode)
UINT32
RO
0x00000384 (900
dec
)
1C33:0B
SM event
missed
counter
as 1C32:11
UINT16
RO
0x0000 (0
dec
)
1C33:0C
Cycle ex-
ceeded
counter
as 1C32:12
UINT16
RO
0x0000 (0
dec
)
1C33:0D
Shift too
short
counter
as 1C32:13
UINT16
RO
0x0000 (0
dec
)
1C33:20
Sync error
as 1C32:32
boolean
RO
0x00 (0
dec
)
4.6.2.3
Profile-specific objects (0x6000-0xFFFF)
The profile-specific objects have the same meaning for all EtherCAT slaves that support profile 5001.
EP9214-0023 and EP9224-0023
94
Version 2.0.0