32 index 1c32 sm output parameter – BECKHOFF EP9214-0023 User Manual
Page 93

Comissioning and Configuration
4.6.2.2.32
Index 1C32 SM output parameter
Index
Name
Meaning
Data type
Flags
Default
1C32:0
SM output
parameter
Synchronization parameters for the outputs
UINT8
RO
0x20 (32
dec
)
1C32:01
Sync mode
Current synchronization mode:
• 0: Free Run
• 1: Synchronous with SM 2 event
• 2: DC-Mode - Synchronous with SYNC0
Event
• 3: DC-Mode - Synchronous with SYNC1 event
UINT16
RW
0x0000 (0
dec
)
1C32:02
Cycle time
Cycle time (in ns):
• Free Run: Cycle time of the local timer
• Synchronous with SM 2 event: Master cycle
time
• DC-Mode: SYNC0/SYNC1 Cycle Time
UINT32
RW
0x000F4240 (1000000
dec
)
1C32:03
Shift time
Time between SYNC0 event and output of the out-
puts (in ns, DC mode only)
UINT32
RO
0x00000384 (900
dec
)
1C32:04
Sync modes
supported
Supported synchronization modes:
• Bit 0 = 1: free run is supported
• Bit 1 = 1: Synchronous with SM 2 event is
supported
• Bit 2-3 = 01: DC mode is supported
• Bit 4-5 = 10: Output shift with SYNC1 event
(only DC mode)
• Bit 14 = 1: dynamic times (measurement
through writing of 1C32:08)
UINT16
RO
0x0001 (1
dec
)
1C32:05
Minimum
cycle time
Minimum cycle time (in ns)
UINT32
RO
0x000F4240 (1000000
dec
)
1C32:06
Calc and
copy time
Minimum time between SYNC0 and SYNC1 event (in
ns, DC mode only)
UINT32
RO
0x00000000 (0
dec
)
1C32:07
Minimum
delay time
UINT32
RO
0x00000384 (900
dec
)
1C32:08
Command
• 0: Measurement of the local cycle time is
stopped
• 1: Measurement of the local cycle time is
started
The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09,
1C33:03, 1C33:06, and 1C33:09 are updated with the
maximum measured values.
For a subsequent measurement the measured values
are reset
UINT16
RW
0x0000 (0
dec
)
1C32:09
Maximum
delay time
Time between SYNC1 event and output of the out-
puts (in ns, DC mode only)
UINT32
RO
0x00000384 (900
dec
)
1C32:0B
SM event
missed
counter
Number of missed SM events in OPERATIONAL (DC
mode only)
UINT16
RO
0x0000 (0
dec
)
1C32:0C
Cycle ex-
ceeded
counter
Number of occasions the cycle time was exceeded in
OPERATIONAL (cycle was not completed in time or
the next cycle began too early)
UINT16
RO
0x0000 (0
dec
)
1C32:0D
Shift too
short
counter
Number of occasions that the interval between
SYNC0 and SYNC1 event was too short (DC mode
only)
UINT16
RO
0x0000 (0
dec
)
1C32:20
Sync error
The synchronization was not correct in the last cycle,
(outputs were output too late; DC mode only)
boolean
RO
0x00 (0
dec
)
EP9214-0023 and EP9224-0023
93
Version 2.0.0