BECKHOFF EP9214-0023 User Manual
Page 103
Comissioning and Configuration
DPO Inputs Device
complete device DPO Inputs Device.
Temperature Warning: The internal temperature
of the EP9224 will soon reach the shut-off point.
Temperature Error: The internal temperature was
too high. The output channels were switched off.
Us/Up Warning: The value of the input voltage
Us/Up is less than 21.5 V
Us/Up Error: The value of the input voltage Us/Up
is less than 18,0V
Global Error Bit:One of the eight channels is
TRUE
Sum Current Warning: The sum value for Is and
Ip of the box set in CoE object F80E:12 has been
exceeded for too long.
Error Sum Current: If the sum value for Is and Ip
of the channel set in CoE object 8000:14 persists,
the channel will be switched off
Reset Input: Reset pin to HIGH (lower M8)
Current Us: Present sum current of the supply
input socket Us
Current Up: Present sum current of the supply
input socket Up
Voltage Us: Present input voltage of the supply
input socket Us in 1/10V
Voltage Up: Present input voltage of the supply
input socket Up in 1/10V
Temperature: Current internal temperature of the
box
DPO Outputs Channel 1 to 4
The EP9214 has 4 x 16-bit output data of the four
output channels DPO Outputs Channel n.
Output Us/Up: TRUE - switch the output on,
FALSE - switch the output off
Reset Us/Up: TRUE - reset in the event of an
error…
DPO Outputs Device
Subsequently, a status word follows for the
complete device DPO outputs Device.
Enable Control Via Fieldbus: TRUE - control all
outputs via the fieldbus / PLC, FALSE - automatic
switch-on depending on the CoE entries
Global Reset: resets all errors in the box
EP9214-0023 and EP9224-0023
103
Version 2.0.0