Analogue outputs configuration – CIRCUTOR CVMk2 Series User Manual

Page 55

background image

55

CVM

k2

CONFIGURA

TION

4.7.3.1. Analogue outputs configuration

The card's analogue outputs configuration screen is shown in the following screen:

The analogue outputs' configuration parameters are:

Var. code

: Real time electric variable code to be assigned to the output (see Chapter 8.3,

Modbus Memory Map, to see the codes for all variables).

Energy code not permitted.

Scale

:

It is possible to select between

0

and

4

, which correspond to scales 0...20 mA

and 4...20 mA, respectively.

Zero

:

The variable should be assigned this value to have an output of 0 or 4 mA

(depends on the scale selected).

Bottom of scale

.: The variable should be assigned this value to have an output of 20 mA.

The function buttons give us the following options when in edit mode:

ESC

: Exit the current menu without saving changes.

OK

: Confirm and save the changes made.

The different buttons that appear on this screen are:

Next

: This button is clicked to increase the output number up to a maximum of 4 (

A/D OUT

04

). Click it again to return to output 01 (

A/D OUT 01

).

IN

: From any screen, click on this button to go to the analogue inputs' configuration

screen. (Section 4.7.3.3. Analogue Inputs Configuration)

EDIT

: Click on this option to access the edit menu. The arrow buttons are used to select the

parameter to be modified (in bold). Enter by pressing the

SET

Button.