Digital inputs configuration – CIRCUTOR CVMk2 Series User Manual
Page 51

51
CVM
k2
CONFIGURA
TION
Edit the two digits in the equation that correspond to the appropriate alarm(s). Between the two
digits corresponding to the alarm, an "*" or "+" sign can be entered. These correspond to the
AND or OR functions, respectively, and will be applied between the alarms configured.
4.7.2.3. Digital inputs configuration
The card inputs are also configured in two different ways depending on whether the user
desires to configure the input as an incremental counter or a two-state logic input (ON/OFF).
size
= 0000
By setting the input size to zero, the input will be configured for ON/OFF input status. When
the input is configured as Boolean, it is not necessary to configure the next menu option,
Dec.
pos
.
size
≠ 0000
When an input size other than zero is configured, this is configured as an incremental pulse
counter, which can have a maximum counter value of 10M. The value to enter is the multiplier
for each input pulse.
Dec. pos:
Indicate the decimal positions that the corresponding input counter should have.
The options available in the lower menu include:
Next
(F2). This increases the input number from 1 to a maximum of 08 to access its
configuration. From the 08 input configuration screen, pressing F2 (
Next
) again
will take the user back to the 01 input configuration screen.
OUT
(F1): Press this button to access the alarms configuration screen, Section 4.7.2.1.
To store the modified parameters in memory, press
SET
and confirm with
OK
(F4). To exit without
saving changes press
ESC
(F3).