CVM
k2
MAINTENANCE / CALIBRA
TION
10. FEATURES
10.2. TECHNICAL FEATURES
10.1. STANDARDS
- CE Marking
- CAT III - 300 / 520 Vac in accordance with EN-61010 Standard.
- Protected against electrical shock by class II double insulation.
- Mounted on the DIN 46227 rail in accordance with EN50022 Standard.
- Energy accuracy according IEC 62053-22
VOLTAGE INPUTS
Minimum measurable voltage
10 V a.c
Measuring range
from 5 to 120% of Un for Un = 300 V a.c. (f-N)
from 5 to 120% of Un for Un = 520 V a.c (f-f)
Frequency
45…65 Hz
Maximum measured voltage
360 Vac
Acceptable overvoltage
750 Vac
Consumption
< 0.6 V•A
CURRENT INPUTS
Minimum measurable current
40 mA
Measuring range
from 1 to 120% of In for In = 5 A
Secondary for the TCs (In)
1 or 5 A
Primary current measured
Programmable < 30.000 A
Acceptable overload
6 A continuous, 100 A t<1 s
Consumption for (.../5 and .../1)
< 0.45 V•A
AUXILIARY POWER SUPPLY
Power supply
85 to 265 Vac (50-60 Hz) (consumption < 30 V·A)
100 to 300 Vdc (consumption < 25 W)
DIGITAL INPUTS
Use voltage
24 V d.c. ± 20%
Minimum signal width
40 ms
Consumption (each input)
< 0.5 W
DIGITAL PULSE OUTPUTS
Type:
Optocoupler
Voltage
150 VDC / 250 VAC
Current
100 mA
Maximum power (per output)
0.8 W
Máximum R
on
35 Ω
RELAY OUTPUTS
Nominal Voltage
230 VAC / 125 VDC
Nominal Current
6 AAC / 1,5 ADC
Máximum load VAC
250 VAC / 6 AAC
Máximum load VDC
30 VDC / 6 ADC
Mínimum load
1 VAC / 1mA
ANALOGUE OUTPUT
Scale
from 0 …. 20 mA or 4 ... 20 mA
Maximum acceptable charge
300 Ω
Response time
< 2 s