5 safety, 6 technical features – CIRCUTOR CVMk2 Series User Manual
Page 19

19
CVM
k2
INST
ALLA
TION
2.4.5 SAFETY
When the system is connected, it may be dangerous to touch the terminals.
Additionally, dangerous parts may be exposed when covers are opened or
when protective components are removed. The system should not be used
until it is completely installed.
To increase system capacity with expansion cards prior to handling, modify
its connections or replace equipment; the power supply should be shut off
and the inputs disconnected from the CVMk2. Handling the system while it
is powered up is dangerous.
2.4.6 TECHNICAL FEATURES
VOLTAGE INPUTS
Measuring range
from 5 to 120% of Un for Un = 300 Vac (f-N)
from 5 to 120% of Un for Un = 520 Vac (f-f)
Frequency
45…65 Hz
Maximum measured voltage
360 Vac
Acceptable overvoltage
750 Vac
Maximum Consumption (limited current) < 0.6 V•A
CURRENT INPUTS
Measuring range
from 1 to 120% of In for In = 5 A
Secondary for the TCs (In)
1 or 5 A
Primary current measured
Programmable < 30.000 A
Acceptable overload
6 A continuous, 100 A t<1 s
Consumption
< 0.45 V•A
AUXILIARY POWER SUPPLY
Power supply
85 to 265 V ac (50...60 Hz) (consumption < 30 V·A)
90 to 300 V dc (consumption < 25 W)
MECHANICAL
Maximum torque
0.8 Nm
Maximum wire rigid diameter
4.5 mm
2
(AWG 11)
Designed for CAT III 300/520 Vac installations in accordance with EN-61010.
Protected against electrical shock by class II double insulation.
Designed and identified by the distinctive CE marks.