5 delete – CIRCUTOR CVMk2 Series User Manual
Page 36

36
CVM
k2
CONFIGURA
TION
Example:
You wish to configure 5 tariff and assign them to
CVMk2 inputs 3, 4, 5 and 6. One expansion
card with static digital inputs is available and inserted in position 2 of the measure module.
Activate 5 tariff and configure the input corresponding to tariff 2 in input
2003
. Accordingly, input
3 in slot 2 will be defined as that which corresponds to tariff 2. The following tariff are configured
in the input: 4, 5 and 6, consecutively.
WARNING: The consecutive tariffs are automatically assigned to the inputs subsequent to the
one configured for tariff 2
4.5 DELETE
CVMk2 has a screen from which parameters, stored to the memory, can be deleted. To access
this display screen, go to the
Setup
menu. In this
menu
, access the
measure
drop-down menu.
Position the cursor over
delete
and confirm by pressing
SET
.
The following entries can be deleted in this menu:
•
all
.:
Delete all stored values. Values that are deleted with this option include:
maximums, minimums, energy meters, maximum demand and input pulse
meters for all of the expansion cards.
•
maximums
: This deletes maximum values stored with the corresponding date and time.
•
minimums
: This deletes minimum values stored with the corresponding date and time.
•
energy
.: Zero the accumulated energy meters, including those for different tariff in the
current, monthly and yearly meters.
Numbers
100X
correspond to the digital inputs for the expansion card inserted in slot 1.
Numbers
200X
correspond to the digital inputs for the expansion card inserted in slot 2, and
numbers
300X
correspond to the digital inputs for the expansion card inserted in slot 3.