CIRCUTOR CVMk2 Series User Manual
Page 145

145
CVM
k2
CHARACTERISTICS
Output range points
4.000
COMMUNICATIONS
Network protocol
RS-485
Communication protocol
Modbus/RTU
Speed (configurable)
9600, 19200, 38400, 57600 baud
Parity
even, odd or no parity
Stop bits
1 or 2
ETHERNET OUTPUT
Network protocol
RJ-45 ETHERNET
Communication protocol
Modbus/TCP
Speed
10baseT / 100baseTx compatible
ENVIRONMENT
Operating temperature
- 10…+ 40 °C
Storage temperature
- 20… + 65ºC
Relative Humidity
95% with no condensation
Facility category
CAT III in accordance with CEI 61010
Degree of contamination
2 in accordance with IEC 61010
Protection index
IP51 front - IP20 rear
For use on a Flat Surface of a Type 1 Enclosure (only for the display module)
MECHANICAL
Connection
Terminal board with screws for rigid 2.5 mm (4.5 mm
2
) or
flexible wires (AWG 11)
Field Wiring terminals to use Copper Conductors only, wire size AWG 14, minimum temperature rating 60º
STANDARDS
EMC
61000-4-2, 61000-4-3, 61000-4-11, 61000-4-4, 61000-4-5
Listed for industrial control equipment miscellaneous
device.
FILE: NMTR E227534
MODEL 405 ACCURACY
( % MEASURE ) ± ( DIGIT )
Currents
± 0,5% ± 1 from 10% to 120% of In
Neutral current
± 0,5% ± 1 from 10% to 120% of In
Voltages
± 0,5% ± 1 from 20% to 120% of Un
Active Power P
± 0,5% ± 1 from 10% to 120% of In
Reactive Power Q
± 0,5% from 10% to 120% of In
Apparent Power S
± 0,5% from 10% to 120% of In
Frecuency
± 0,01 Hz from 45 to 65 Hz
Active Energy
± 0,5%
Reactive Energy
± 0,5%
MODEL 402 ACCURACY
( % MEASURE ) ± ( DIGIT )
Currents
± 0,2% ± 2 from 10% to 120% of In
Neutral current
± 0,5% ± 1 from 10% to 120% of In
Voltages
± 0,2% ± 2 from 20% to 120% of Un
Active Power P
± 0,2% ± 1 from 10 % to 120% of In
Reactive Power Q
± 0,5% from 10% al 120% of In
Apparent Power S
± 0,5% from 10% al 120% of In
Frecuency
± 0,01 Hz from 45 to 65 Hz
Active Energy
± 0,2%
Reactive Energy
± 0,5%