8.3.3. ENERGY VARIABLES FROM PREVIOUS PERIODS
PREVIOUS MONTH MODBUS ENERGY VARIABLES
VARIABLE
SYMBOL
KW·H
W·H
TARIFF 1
Active energy
kW·h III
600-601
602
Inductive reactive energy
kvar·h L III
603-604
605
Capacitive reactive energy
kvar·h C III
606-607
608
Three phase apparent energy
kV·A·hIII
609-60A
60B
Active energy generated
kW·hIII (-)
60C-60D
60E
Inductive energy generated
kvar·h LIII (-)
60F-610
611
Capacitive energy generated
kvar·h CIII (-)
612-613
614
Apparent energy generated
kV·A·hIII (-)
615-616
617
TARIFF 2
Active energy
kW·h III
618-619
61A
Inductive reactive energy
kvar·h L III
61B-61C
61D
Capacitive reactive energy
kvar·h C III
61E-61F
620
Three phase apparent energy
kV·A·hIII
621-622
623
Active energy generated
kW·hIII (-)
624-625
626
Inductive energy generated
kvar·h LIII (-)
627-628
629
Capacitive energy generated
kvar·h CIII (-)
62A-62B
62C
Apparent energy generated
kV·A·hIII (-)
62D-62E
62F
TARIFF 3
Active energy
kW·h III
630-631
632
Inductive reactive energy
kvar·h L III
633-634
635
Capacitive reactive energy
kvar·h C III
636-637
638
Three phase apparent energy
kV·A·hIII
639-63A
63B
Active energy generated
kW·hIII (-)
63C-63D
63E
Inductive energy generated
kvar·h LIII (-)
63F-640
641
Capacitive energy generated
kvar·h CIII (-)
642-643
644
Apparent energy generated
kV·A·hIII (-)
645-646
647
TARIFF 4
Active energy
kW·h III
648-649
64A
Inductive reactive energy
kvar·h L III
64B-64C
64D
Capacitive reactive energy
kvar·h C III
64E-64F
650
Three phase apparent energy
kV·A·hIII
651-652
653
Active energy generated
kW·hIII (-)
654-655
656
Inductive energy generated
kvar·h LIII (-)
657-658
659
Active energy generated
kW·hIII (-)
205
5E4-5E5
5E6
Inductive energy generated
kvar·h LIII (-)
206
5E7-5E8
5E9
Capacitive energy generated
kvar·h CIII (-)
207
5EA-5EB
5EC
Apparent energy generated
kV·A·hIII (-)
208
5ED-5EE