beautypg.com

YSI 5200A User Manual

Page 29

background image

YSI 5200A

57

YSI 5200A

56

Wire all slaves as follows:

Wire Color

Terminal

solid blue

T (-)

white with blue stripe

T (+)

solid orange

R (-)

white with orange stripe

R (+)

green

Communications

Common

(C)

Figure 3.26 is a wiring diagram for the most common 5200A network configuration

where a master 5200A is the first physical device in the network.

Figure 3.26

6. Wire all network terminal strips prior to network testing, but only con-

nect a network terminal strip to the first and last devices on the network

(*see note below). Configure network menu and follow testing procedure

as described - page 96. Slave devices are tested one by one as they are

added to the network. Network testing cannot be done if stubs exist (**

see note below).

Notes:

- *If the master is not the first physical device on the network, place network

terminal strip on the master and on the first and last physical devices on

the network. (In this case two slaves will need to be tested at the same

time.) - figure 3.27.

- **A stub is created when the last wired network terminal strip is not con-

nected to a network slave - figure 3.24.

Installation and Wiring

master

Testing network configurations

slave

master

slave

slave

slave

-represents wired network termination strip

-terminal strips that appear within master/slave box represent terminal strips that are physically

connected to device

-terminal strips that appear outside slave box represent terminal strips not connected to device

When master is first physical device on network, as shown above, connect terminal strip to master and last

slave (slave 4) to begin network testing. Terminal strips for slaves located between the master and the last

slave are then connected, one, by one beginning with slave device furthest from master and continuing to

slave devices closest to master. Testing in the above graphic would occur first with slave 4, then slave 3,

then slave 2, ending with slave 1.

slave

slave

slave

slave

-represents wired network termination strip

-terminal strips that appear within master/slave box represent terminal strips that are physically

connected to device

-terminal strips that appear outside slave box represent terminal strips not connected to device

When master is not the first physical device on network, as shown above, connect terminal strip to master

and outer most slaves (slaves 1 and 4) to begin network testing. Testing in above graphic would occur first

with slaves 1 and 4, and then continuing by testing slave device 2, or slave device 3 until all network

wiring is tested.

Use below network wiring testing method when master is not first physical device on network.

Use below network wiring testing method when master is first physical device on network.

Follow wiring instructions below to avoid testing network wiring with stubs.

1

2

3

4

1

2

3

4

Figure 3.27

7. Close front panel - page 40.

5200A networks must be configured point-to-point (instrument-to-instrument).

Network wiring cannot contain loops, stars, or stubs - figure 3.28.

Installation and Wiring