beautypg.com

Circulating air supply, Air ducts, Unconditioned spaces – Reznor R8HE Unit Installation Manual User Manual

Page 7: Acoustical duct work, Unit installation, Packaging removal, Rigging & hoisting, Warning

background image

7

CIRCULATING AIR SUPPLY

WARNING:

Products of combustion must not be allowed to

enter the return air ductwork or the circulating air

supply. Failure to prevent products of combustion

from being circulated into the living space can

create potentially hazardous conditions including

carbon monoxide poisoning that could result in

personal injury or death.
All return ductwork must be adequately sealed,

all joints must be taped, and the ductwork must

be secured to the unit with sheet metal screws.

When return air is provided through the bottom

of the unit, the joint between the unit and the

return air plenum must be air tight.
The roof curb or cement pad that the unit is

mounted must provide sound physical support of

the unit with no gaps, cracks, or sagging bewteen

the unit and pad.
Return air and circulating air ductwork must not

be connected to any other heat producing device

such as a fireplace insert, stove, etc. Doing so

may result in fire, explosion, carbon monoxide

poisoning, personal injury, or property damage.

Air Ducts

This unit is designed only for use with a supply and return

duct. Air ducts should be installed in accordance with the

standards of the National Fire Protection Association

“Standard for Installation of Air Conditioning Systems”

(NFPA 90A), “Standard for Installation of Residence Type

Warm Air Heating and Air Conditioning Systems” (NFPA

90B), and all applicable local codes. NFPA publications

are available by writing to: National Fire Protection

Association, Batterymarch Park, Quincy, ME 02269 or

visit www.NFPA.org on the web.
• Design the duct work according to Manual D by the Air

Conditioning Contractors of America (ACCA).

• The ducts must be properly sized not to exceed the

units maximum ESP rating at 400 SCFM per nominal

ton of cooling capacity.

• Duct work should be attached directly to the unit flanges

for horizontal applications.

• If a roof curb is installed, the ducts must be attached to

the curb hangers, not the unit.

• It is recommended that the outlet duct be provided

with a removable access panel. The opening should

be accessible when the unit is installed in service and

shall be sizes so that smoke or reflected light may be

observed inside the casing to indicate the presence of

leaks in the heat exchanger. The cover for the opening

shall be attached in a way that will prevent leaks.

• If outside air is utilized as return air to the unit for

ventilation or to improve indoor air quality, the system

must be designed so that the return air to the unit is not

less than 50° F (10° C) during heating operation.

• If a combination of indoor and outdoor air is used, the

ducts and damper system must be designed so that the

return air supply to the furnace is equal to the return air

supply under normal, indoor return air applications.

Unconditioned Spaces

All duct work passing through unconditioned space must

be properly insulated to minimize duct losses and prevent

condensation. Use insulation with an outer vapor barrier.

Refer to local codes for insulation material requirements.

Acoustical Duct Work

Certain installations may require the use of acoustical

lining inside the supply duct work.

• Acoustical insulation must be in accordance with the

current revision of the Sheet Metal and Air Conditioning

Contractors National Association (SMACNA) application

standard for duct liners.

• Duct lining must be UL classified batts or blankets with

a fire hazard classification of FHC-25/50 or less.

• Fiber duct work may be used in place of internal duct

liners if the fiber duct work is in accordance with the

current revision of the SMACNA construction standard

on fibrous glass ducts. Fibrous duct work and internal

acoustical lining must be NFPA Class 1 air ducts when

tested per UL Standard 181 for Class 1 ducts.

UNIT INSTALLATION

Packaging Removal

Remove the shipping carton and User’s Manual from the

equipment. Set aside the 13” x 2” PVC pipe for later use

when installing the heat exchanger condensate drain and

vent kit. Take care not to damage the coil or cabinet when

removing the carton. For rooftop installations, remove
and discard the two supports attached beneath the unit

Rigging & Hoisting

WARNING:

To avoid the risk of property damage, personal

injury, or death, it is the rigger’s responsibility

to ensure that whatever means are used to hoist

the unit are safe and adequate:
• The lifting equipment must be adequate for the

load. Refer to

Table 7 (page 27)

for unit weights.

• The unit must be lifted from the holes in the

base rails using cables or chains.

• Spreader bars are required to protect the unit

and ensure even loading.

• Keep the unit in an upright position at all times.

The rigging must be located outside the units

center of gravity. Refer to

Figure 7 (page 20)

for locating the center of gravity.

• All panels must be securely in place during

rigging and hoisting, except control access

panel. See

page 48

for additional lifting and

setting of unit requirements.