beautypg.com

Electrical wiring, Pre-electrical checklist, Grounding – Reznor R8HE Unit Installation Manual User Manual

Page 11: Line voltage, Warning, Avertissement

background image

11

ELECTRICAL WIRING

WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could

result in serious injury or property damage.
Improper servicing could result in dangerous

operation, serious injury, death or property

damage.
• Before servicing, disconnect all electrical

power to furnace.

• When servicing controls, label all wires prior

to disconnecting. Reconnect wires correctly.

• Verify proper operation after servicing.”

AVERTISSEMENT:

RISQUE DE CHOC ÉLECTRIQUE,

D’INCENDIE OU D’EXPLOSION

Le non-respect des avertissements de

sécurité pourrait entraîner un fonctionnement

dangereux de l’appareil, des blessures graves,

la mort ou des dommages matériels.
Un entretein incorrect pourrait entraîner un

fonctionnement dangereux de l’appareil, des

blessures graves, la mort ou des dommages

matériels
• Couper toute alimentation électrique au

générateur d’air chaud avant de prodéder
aux travaux d’entretein.

• Au moment de l’entretien des commandes,

étiquetez tous les fils avant de les débrancher.
S’assurer de les raccorder correctement.

• S’assurer que l’appareil fonctionne

adéquatement aprés l’entretien.

• Electrical connections must be in compliance with all

applicable local codes with the current revision of the

National Electric Code (ANSI/NFPA 70).

• For Canadian installations the electrical connections

and grounding shall comply with the current Canadian

Electrical Code (CSA C22.1 and/or local codes).

IMPORTANT NOTE:

If replacing any of the original wires supplied with the

furnace, the replacement wire must be copper wiring

having the same guage, voltage, and temperature

rating.

Pre-Electrical Checklist
(Single & 3-Phase Models)

√ Verify the voltage, frequency, and phase of the supply

source match the specifications on the unit rating plate.

√ Verify that the service provided by the utility is sufficient

to handle the additional load imposed by this equipment.
See

Table 16 (page 35)

(or the unit rating label) for

proper high voltage wiring requirements.

√ Verify factory wiring is in accordance with the unit wiring

diagram.

Figure 13 (page 37)

,

Figure 14 (page 38)

,

&

Figure 15 (page 39)

. Make sure the connections

didn’t loosen during shipping or installation.

Phase balance on 3 phase units must always be

checked. See Unbalanced 3-Phase Supply Voltage
section (

page 12

).

Grounding

WARNING:

The unit cabinet must have an uninterrupted or

unbroken electrical ground to minimize personal

injury if an electrical fault should occur. Do not

use gas piping as an electrical ground!

This unit must be electrically grounded in accordance with

local codes or, in the absence of local codes, with the

National Electrical Code (ANSI/NFPA 70) or the CSA C22.1

Electrical Code. Grounding of the unit is accomplished

by using the grounding lug provided in the control box.

Line Voltage

• The line voltage to the unit should be supplied from a

dedicated branch circuit containing the correct fuse or

circuit breaker for the unit.

An electrical disconnect must be located within sight

of and readily accessible to the unit. This switch shall

be capable of electrically de-energizing the outdoor unit.

See unit data label for proper incoming field wiring. Any

other wiring methods must be acceptable to authority

having jurisdiction.

• Use only copper wire for the line voltage power supply

to this unit. See

Table 17 (page 35)

. Use proper

code agency listed conduit and a conduit connector

for connecting the supply wires to the unit. Use of rain

tight conduit is recommended.

• Provide power supply for the unit in accordance with

the unit wiring diagram and the unit rating plate.

• Overcurrent protection must be provided at the branch

circuit distribution panel and sized as shown on the unit

rating label and according to applicable local codes.
See

Table 16 (page 35)

or the unit rating plate for

minimum circuit ampacity and maximum overcurrent

protection limits.

• A wiring diagram is located on the inside cover of the

control access panel of the outdoor unit. The installer

should become familiar with the wiring diagram before

making any electrical connections to the outdoor unit.
See

Figure 13 (page 37)

,

Figure 14 (page 38)

, &

Figure 15 (page 39)

.