Table 10. blower performance - 2 & 2.5 ton, Table 10, 208 volt operation – Reznor R8HE Unit Installation Manual User Manual

Page 29

background image

29

R8HE / PPG3HE -X24K060XA / -X30K060XA

60,000 BTUH, 30” CABINET, 11”X8” BLOWER W- 3/4 HP ECM MOTOR

230 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

824

64

782

67

740

71

697

76

653

81

611

86

568

93

529

100

489

108

1

0

0

0

894

59

852

62

810

65

766

69

722

73

681

78

640

82

601

88

562

94

0

1

0

0

964

55

922

57

880

60

836

63

791

67

752

70

712

74

674

78

635

83

1

1

0

0

1039

51

997

53

956

55

915

58

874

60

833

63

793

67

754

70

716

74

0

0

1

0

1113

47

1073

49

1032

51

995

53

957

55

915

58

873

60

835

63

797

66

1

0

1

0

1168

45

1128

47

1088

49

1051

50

1014

52

973

54

932

57

894

59

857

62

0

1

1

0

1222

43

1183

45

1144

46

1107

48

1070

49

1031

51

991

53

954

55

916

58

1

1

1

0 1283

41

1246

42

1209

44

1158

46

1107

48

1081

49

1054

50

1015

52

975

54

0

0

0

1

1343

39

1308

40

1273

41

1209

44

1144

46

1131

47

1117

47

1076

49

1034

51

1

0

0

1

1393

38

1358

39

1324

40

1273

41

1223

43

1196

44

1169

45

1128

47

1088

49

0

1

0

1

1443

37

1409

37

1374

38

1338

39

1301

41

1261

42

1220

43

1181

45

1142

46

1

1

0

1

1482

36

1446

37

1410

37

1374

38

1339

39

1300

41

1261

42

1223

43

1185

45

0

0

1

1

1521

35

1483

36

1445

37

1411

37

1376

38

1339

39

1301

41

1264

42

1227

43

1

0

1

1

1560

34

1522

35

1485

36

1450

36

1416

37

1378

38

1340

39

1303

40

1267

42

0

1

1

1

1598

33

1562

34

1525

35

1490

35

1455

36

1417

37

1379

38

1343

39

1306

40

1

1

1

1

1633

32

1595

33

1557

34

1524

35

1490

35

1458

36

1426

37

1390

38

1353

39

208 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

783

67

740

71

696

76

645

82

594

89

554

95

514

103

472

112

429

123

1

0

0

0

851

62

808

65

765

69

719

73

672

79

631

84

590

90

549

96

509

104

0

1

0

0

919

57

877

60

834

63

792

67

750

70

708

75

665

79

627

84

588

90

1

1

0

0

994

53

953

55

913

58

871

61

830

64

785

67

741

71

702

75

664

79

0

0

1

0

1068

49

1030

51

991

53

950

56

909

58

863

61

816

65

778

68

740

71

1

0

1

0

1122

47

1084

49

1046

50

1005

53

964

55

920

57

876

60

837

63

797

66

0

1

1

0

1175

45

1138

46

1101

48

1060

50

1018

52

977

54

936

56

895

59

854

62

1

1

1

0 1237

43

1198

44

1159

46

1120

47

1082

49

1040

51

999

53

957

55

916

58

0

0

0

1

1299

41

1258

42

1216

43

1181

45

1146

46

1104

48

1061

50

1020

52

978

54

1

0

0

1

1349

39

1308

40

1267

42

1232

43

1197

44

1156

46

1115

47

1072

49

1030

51

0

1

0

1

1398

38

1358

39

1318

40

1283

41

1248

42

1208

44

1168

45

1125

47

1082

49

1

1

0

1

1440

37

1398

38

1357

39

1322

40

1288

41

1247

42

1206

44

1163

45

1121

47

0

0

1

1

1481

36

1439

37

1396

38

1362

39

1327

40

1285

41

1243

42

1202

44

1160

45

1

0

1

1

1516

35

1476

36

1436

37

1400

38

1365

39

1325

40

1285

41

1247

42

1209

44

0

1

1

1

1550

34

1513

35

1475

36

1439

37

1402

38

1365

39

1327

40

1292

41

1257

42

1

1

1

1

1581

33

1544

34

1507

35

1476

36

1444

37

1410

37

1375

38

1332

40

1289

41

NOTES:

1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.

2. Temperature rises in tables are approximate. Actual temperature rises may vary.

3. Shaded areas are not recommended or approved for proper heating operation of equipment.

Heat rise: Btu/h (Input) = CFM * Δ T * 1.08

Δ T = (Btu/h * 0.95) / (CFM * 1.08)

Table 10. Blower Performance - 2 & 2.5 Ton