Start up & adjustments, Pre-start check list, Start-up procedure – Reznor R8HE Unit Installation Manual User Manual

Page 18: Air circulation, Lighting the appliance, Warning, Avertissement

background image

18

START UP & ADJUSTMENTS

Pre-Start Check List

√ Verify the unit is level and allows evaporator condensate

to drain.

√ Verify heat exchanger condensate drain and vent kit

have been installed according to the instructions included

with horizontal kit 922323 or downflow kit 922485 or as
described in the Appendix section (

page 43

).

√ Verify all clearance requirements are met and there is

free airflow to and from the outdoor coil.

√ Verify that the duct work is sealed to prevent air leakage

and air filter is installed.

√ Verify that the line voltage power leads are securely

connected and the unit is properly grounded.

√ Verify that the low voltage wires are securely connected

to the correct terminals in the low voltage area of the

control box.

√ Verify that the gas line service pressure does not exceed

10.0 inches WC (0.36 psig), and is not less than 4.5

inches WC (0.16 psig) for natural gas. For LP gas the

line service pressure must not exceed 14 inches WC

(0.51 psig) and must not be less than 11.0 inches WC

(0.40 psig).

√ Verify that the flame roll-out control is closed. If

necessary, press the red button to reset the control.

DO

NOT install a jumper wire across the control to defeat its

function. If the control reopens upon start-up,

DO NOT

reset the control without identifying and correcting the

fault condition which caused the control to trip.

√ Verify that the gas line has been purged and all

connections are leak tight.

√ Verify that all exterior panels are replaced and securely

fastened.

√ Verify that the outdoor fan turns freely.

√ Verify that the power supply branch circuit overcurrent

protection is sized properly.

√ Verify that the thermostat is wired correctly. The

thermostat function switch should be set to OFF and

the thermostat fan switch should be set to AUTO.

Start-Up Procedure

WARNING:

If this unit is equipped with crankcase heaters,

allow 24 hrs for heating of the refrigerant

compressor crankcase prior to start up or anytime

the power has been removed for more than 12

hrs. Failure to comply may result in damage or

cause premature failure of the system.

Air Circulation

Leave the thermostat system mode on OFF, and set the

fan mode to ON. Blower should run continuously. Check

the air delivery at the supply registers and adjust register

openings for balanced air distribution. Examine ductwork

for leaks or obstruction if insufficient air is detected. Set

the thermostat fan mode to AUTO. The blower should

stop running.

NOTE: When FAN ON is selected, the blower will operate

at 50% of selected airflow when no call for heating or

cooling is present.

Lighting the Appliance

WARNING:

FIRE OR EXPLOSION HAZARD

• Failure to follow safety warnings exactly could

result in serious injury or property damage.

• Installation and service must be performed

by a qualified installer, service agency or the

gas supplier.

• Do not store or use gasoline or other flammable

vapors and liquids in the vicinity of this or any
other appliance.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use

any phone in your building.

• Leave the building immediately.
• Immediately call your gas supplier from a

neighbor’s phone. Follow the gas supplier’s

instructions.

• If you cannot reach your gas supplier, call the

fire department.

AVERTISSEMENT:

RISQUE D’INCENDIE OU D’ EXPLOSION

• Le non-respect des avertissements de sécurité

pourrait entraîner des blessures graves, la

mort ou des dommages matériels.

• L’installation et l’entretien doivent être

effectués par un installateur qualifié, un

organisme de service ou le fournisseur de

gazstaller, service agency or the gas supplier.

• Ne pas entreposer ni utiliser de l’essence ni

d’autres vapeurs ou liquides inflammables

dans le voisinage de cet appareil, ni de tout

autre appareil.

QUE FAIRE S’IL Y A UNE ODEUR DE GAZ

• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;

n’utiliser aucun téléphone dans le bâtiment.

• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de

gaz en employant le téléphone d’un voisin.

Respecter à la lettre les instructions du

fournisseur de gaz.

• Si personne ne répond, appeler le service des

incendies.