Start up & adjustments, Pre-start check list, Start-up procedure – Reznor R8HE Unit Installation Manual User Manual
Page 18: Air circulation, Lighting the appliance, Warning, Avertissement
18
START UP & ADJUSTMENTS
Pre-Start Check List
√ Verify the unit is level and allows evaporator condensate
to drain.
√ Verify heat exchanger condensate drain and vent kit
have been installed according to the instructions included
with horizontal kit 922323 or downflow kit 922485 or as
described in the Appendix section (
√ Verify all clearance requirements are met and there is
free airflow to and from the outdoor coil.
√ Verify that the duct work is sealed to prevent air leakage
and air filter is installed.
√ Verify that the line voltage power leads are securely
connected and the unit is properly grounded.
√ Verify that the low voltage wires are securely connected
to the correct terminals in the low voltage area of the
control box.
√ Verify that the gas line service pressure does not exceed
10.0 inches WC (0.36 psig), and is not less than 4.5
inches WC (0.16 psig) for natural gas. For LP gas the
line service pressure must not exceed 14 inches WC
(0.51 psig) and must not be less than 11.0 inches WC
(0.40 psig).
√ Verify that the flame roll-out control is closed. If
necessary, press the red button to reset the control.
DO
NOT install a jumper wire across the control to defeat its
function. If the control reopens upon start-up,
DO NOT
reset the control without identifying and correcting the
fault condition which caused the control to trip.
√ Verify that the gas line has been purged and all
connections are leak tight.
√ Verify that all exterior panels are replaced and securely
fastened.
√ Verify that the outdoor fan turns freely.
√ Verify that the power supply branch circuit overcurrent
protection is sized properly.
√ Verify that the thermostat is wired correctly. The
thermostat function switch should be set to OFF and
the thermostat fan switch should be set to AUTO.
Start-Up Procedure
WARNING:
If this unit is equipped with crankcase heaters,
allow 24 hrs for heating of the refrigerant
compressor crankcase prior to start up or anytime
the power has been removed for more than 12
hrs. Failure to comply may result in damage or
cause premature failure of the system.
Air Circulation
Leave the thermostat system mode on OFF, and set the
fan mode to ON. Blower should run continuously. Check
the air delivery at the supply registers and adjust register
openings for balanced air distribution. Examine ductwork
for leaks or obstruction if insufficient air is detected. Set
the thermostat fan mode to AUTO. The blower should
stop running.
NOTE: When FAN ON is selected, the blower will operate
at 50% of selected airflow when no call for heating or
cooling is present.
Lighting the Appliance
WARNING:
FIRE OR EXPLOSION HAZARD
• Failure to follow safety warnings exactly could
result in serious injury or property damage.
• Installation and service must be performed
by a qualified installer, service agency or the
gas supplier.
• Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Leave the building immediately.
• Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions.
• If you cannot reach your gas supplier, call the
fire department.
AVERTISSEMENT:
RISQUE D’INCENDIE OU D’ EXPLOSION
• Le non-respect des avertissements de sécurité
pourrait entraîner des blessures graves, la
mort ou des dommages matériels.
• L’installation et l’entretien doivent être
effectués par un installateur qualifié, un
organisme de service ou le fournisseur de
gazstaller, service agency or the gas supplier.
• Ne pas entreposer ni utiliser de l’essence ni
d’autres vapeurs ou liquides inflammables
dans le voisinage de cet appareil, ni de tout
autre appareil.
QUE FAIRE S’IL Y A UNE ODEUR DE GAZ
• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;
n’utiliser aucun téléphone dans le bâtiment.
• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de
gaz en employant le téléphone d’un voisin.
Respecter à la lettre les instructions du
fournisseur de gaz.
• Si personne ne répond, appeler le service des
incendies.