Airflow Information

Table 8. Cooling Airflow Settings

SWITCH

SETTING

RECOMMENDED

AIRFLOW (CFM)

SWITCH

SETTING

RECOMMENDED

AIRFLOW (CFM)

5 6 7 8

5 6 7 8

0 0 0 0

2

T

O

N

800

0 0 0 0

800

1 0 0 0

875

1 0 0 0

2.5

T

O

N

875

0 1 0 0

925

0 1 0 0

925

1 1 0 0

1000

1 1 0 0

1000

0 0 1 0

1075

0 0 1 0

1075

1 0 1 0

1125

1 0 1 0

1125

0 1 1 0

1175

0 1 1 0

1175

1 1 1 0

1225

1 1 1 0

1225

0 0 0 1

1300

0 0 0 1

1300

1 0 0 1

1350

1 0 0 1

1350

0 1 0 1

1400

0 1 0 1

1400

1 1 0 1

1450

1 1 0 1

1450

0 0 1 1

1500

0 0 1 1

1500

1 0 1 1

1525

1 0 1 1

1525

0 1 1 1

1560

0 1 1 1

1560

1 1 1 1

1600

1 1 1 1

1600

SWITCH

SETTING

RECOMMENDED

AIRFLOW (CFM)

SWITCH

SETTING

RECOMMENDED

AIRFLOW (CFM)

5 6 7 8

5 6 7 8

0 0 0 0

3

T

O

N

1110

0 0 0 0

1180

1 0 0 0

1145

1 0 0 0

3.5

T

O

N

1250

0 1 0 0

1180

0 1 0 0

1320

1 1 0 0

1215

1 1 0 0

1380

0 0 1 0

1250

0 0 1 0

1440

1 0 1 0

1285

1 0 1 0

1500

0 1 1 0

1320

0 1 1 0

1560

1 1 1 0

1355

1 1 1 0

1610

0 0 0 1

1390

0 0 0 1

1660

1 0 0 1

1430

1 0 0 1

1710

0 1 0 1

1480

0 1 0 1

1740

1 1 0 1

1525

1 1 0 1

1770

0 0 1 1

1575

0 0 1 1

1800

1 0 1 1

1625

1 0 1 1

1830

0 1 1 1

1675

0 1 1 1

1860

1 1 1 1

1725

1 1 1 1

1895

SWITCH

SETTING

RECOMMENDED

AIRFLOW (CFM)

SWITCH

SETTING

RECOMMENDED

AIRFLOW (CFM)

5 6 7 8

5 6 7 8

0 0 0 0

1180

0 0 0 0

1180

1 0 0 0

4

T

O

N

1250

1 0 0 0

1250

0 1 0 0

1320

0 1 0 0

1320

1 1 0 0

1380

1 1 0 0

5

T

O

N

1380

0 0 1 0

1440

0 0 1 0

1440

1 0 1 0

1500

1 0 1 0

1500

0 1 1 0

1560

0 1 1 0

1560

1 1 1 0

1610

1 1 1 0

1610

0 0 0 1

1660

0 0 0 1

1660

1 0 0 1

1710

1 0 0 1

1710

0 1 0 1

1740

0 1 0 1

1740

1 1 0 1

1770

1 1 0 1

1770

0 0 1 1

1800

0 0 1 1

1800

1 0 1 1

1830

1 0 1 1

1830

0 1 1 1

1860

0 1 1 1

1860

1 1 1 1

1895

1 1 1 1

1895

NOTE: Factory settings & recommended operating range are

highlighted in bold / italics.

SWITCH

SETTING

2 & 2.5 TON

CFM

SWITCH

SETTING

3.5 TON

CFM

LOW

HEAT

HIGH

HEAT

LOW

HEAT

HIGH

HEAT

39,000

60,000

52,000

80,000

1 2 3 4 CFM RISE CFM RISE

1 2 3 4 CFM RISE CFM RISE

0 0 0 0 600

57

800

66

0 0 0 0 885

55

1180 64

1 0 0 0 656

52

875

60

1 0 0 0 938

52

1250 61

0 1 0 0 694

49

925

57

0 1 0 0 990

49

1320 58

1 1 0 0 750

46

1000 53

1 1 0 0 1035

47

1380 55

0 0 1 0 806

43

1075 49

0 0 1 0 1080

45

1440 53

1 0 1 0 844

41

1125 47

1 0 1 0 1125

43

1500 51

0 1 1 0 881

39

1175 45

0 1 1 0 1170 42 1560 49

1 1 1 0 919 37 1225 43

1 1 1 0 1208

41

1610 47

0 0 0 1 975

35

1300 40

0 0 0 1 1245

40

1660 45

1 0 0 1 1013

34

1350 39

1 0 0 1 1283

39

1710 44

0 1 0 1 1050

33

1400 38

0 1 0 1 1305

38

1740 43

1 1 0 1 1088

32

1450 36

1 1 0 1 1328

37

1770 42

0 0 1 1 1125

30

1500 35

0 0 1 1 1350

36

1800 41

1 0 1 1 1144

30

1525 35

1 0 1 1 1373

35

1830 40

0 1 1 1 1170

29

1560 34

0 1 1 1 1395

34

1860 39

1 1 1 1 1200

29

1600 33

1 1 1 1 1421

34

1895 39

SWITCH

SETTING

3 TON

CFM

SWITCH

SETTING

4 & 5 TON

CFM

LOW

HEAT

HIGH

HEAT

LOW

HEAT

HIGH

HEAT

52,000

80,000

62,400

96,000

1 2 3 4 CFM RISE CFM RISE

1 2 3 4 CFM RISE CFM RISE

0 0 0 0 833

55

1110 63

0 0 0 0 885

62

1180 73

1 0 0 0 859

53

1145 61

1 0 0 0 938

59

1250 70

0 1 0 0 885

52

1180 60

0 1 0 0 990

55

1320 67

1 1 0 0 911

50

1215 58

1 1 0 0 1035

53

1380 65

0 0 1 0 938

49

1250 56

0 0 1 0 1080

51

1440 63

1 0 1 0 964

47

1285 55

1 0 1 0 1125

49

1500 61

0 1 1 0 990

46

1320 53

0 1 1 0 1170

47

1560 59

1 1 1 0 1016

45

1355 52

1 1 1 0 1208

46

1610 57

0 0 0 1 1043 44 1390 50

0 0 0 1 1245

45

1660 55

1 0 0 1 1073

43

1430 49

1 0 0 1 1283

44

1710 54

0 1 0 1 1110

41

1480 48

0 1 0 1 1305 43 1740 53

1 1 0 1 1144

40

1525 46

1 1 0 1 1328

42

1770 52

0 0 1 1 1181

39

1575 45

0 0 1 1 1350

41

1800 51

1 0 1 1 1219

38

1625 43

1 0 1 1 1373

40

1830 50

0 1 1 1 1256

36

1675 42

0 1 1 1 1395

39

1860 49

1 1 1 1 1294

35

1725 41

1 1 1 1 1421

39

1895 48

NOTES:

1. Factory settings are bold / italicized. Use of any other switch setting may result

in nuisance trips and should be verified for the application.

2. Temperature rises in tables are approximate. Actual temperature rises may

vary.

3. Shaded areas are not approved for proper operation of equipment.

Table 9. Heating Airflow Settings