Blocked Vent / Condensate Disposal Shut
Down

The pressure switch is constantly monitored throughout

the ignition cycle. After normal operation is established,

if the pressure switch opens for more than 2-3 seconds,

the unit will shutdown and go into a 1 hour lockout. The

control will de-energize the gas valve and inducer motor

after normal post purge timing, energize the main blower,

and store the fault in non-volatile memory. The blower

stays energized for the selected blower off delay period.

The ignition control will display a flash code of Green-OFF

/ Red-Flash to indicate system fault for “Pressure Switch

Loss Due To Blocked Vent / Condensate Disposal”. One

hour lockout period can be terminated by shutting off the

thermostat for 5-10 seconds or main power to unit for

1-2 seconds.
After expiration of the 1 hour lockout period or manual

reset, the control will attempt a new ignition cycle. If the

pressure switch fails to close on first ignition attempt of

one minute burn time and a non-volatile condensate/vent

fault is set, control will go back to lockout and display the

condensate/vent fault flash code. Fault remains stored in

non-volatile memory even with cycling of thermostat or

main power.

NOTE: Nonvolatile blocked condensate/

vent fault will be cleared when a complete thermostat

heat demand is satisfied in steady state heat mode.

Cooling Mode - Single Stage Operation

1. On a call for cooling, the thermostat closes applying 24

VAC to the

G & Y terminals on the low voltage terminal

strip.

2. The

G terminal applies 24VAC to the G terminal of the

integrated control, energizing the main circulating blower

circuit at the selected cooling speed.

3. The

Y terminal applies 24VAC to the contactor energizing

the outdoor compressor and fan.

4. When the thermostat is satisfied, the contactor and

integrated control de-energize. Compressor and outdoor

fan will stop running.

5. The circulating blower motor de-energizes after a 60

second delay.

De-Humidification Control

If installing a humidistat, install it in the return air duct

as directed in the installation instructions included in the

accessory kit. Run the humidistat wiring through the low

voltage wire entrance of the packaged unit. Connect one

side of the humidistat to the

R terminal of the low voltage

field connection board and connect the other side to the

DEHUM terminal on the blower control board. Wire the

humidistat to close on rise in humidity.

For dehumidification, the

DEHUM input on the FSHE

board (

Figure 11 (page 36)

) can be used to control

this function. If the

DEHUM input is active and the unit

is operating, the blower CFM is 75% of cooling for the

operating speed.

Fan Mode

1. On a call for fan only operation, the thermostat applies

24 VAC to the

G terminal connected to the G terminal

of the integrated control.

2. The circulating blower is energized immediately and

will operate approximately 50% of the selected airflow

when no call for heqating or cooling is present

.

NOTE: If a call for heat occurs, the circulating blower

de-energizes prior to normal heating cycle.

COMPONENT FUNCTIONS

Flame Roll-Out Control - The flame roll-out control acts

to verify that the burner flame is being drawn into the heat

exchanger tubes. If the burner flame is not being drawn

into the heat exchanger tubes, the roll-out control will

open within several seconds and the integrated control

diagnostic light will flash one time. The circulating air

blower and combustion blower will continue to operate if

the flame roll-out control opens.
Flame Sensor - The flame sensor acts to prove that

flame has carried over from the ignitor to the right-most

burner. If no flame is sensed, the unit will be shut down

automatically.
Gas Valve - The gas valve controls the flow of gas to the

burners. When the gas valve is energized it automatically

opens and regulates the gas pressure in the manifold.
Inducer Hall Effect Sensor Switch - This sensor verifies

the inducer motor is running in the event of power outages

or during long intervals of unit off time where pressure

switch reading could be lost due to ice formation over

the pressure switch port. This will clear within the first or

second thaw cycle routine.
Pressure Switch - The pressure switch verifies that the

inducer motor is drawing the combustion gases through

the heat exchanger tubes and venting the gases through

the vent system.
Over-Temperature Limit Control - The over-temperature

limit control prevents the air temperature leaving the unit

from exceeding the maximum outlet air temperature.

If the limit opens, the integrated control diagnostic will

flash one time. The circulating air blower and combustion

blower will continue to operate if the over-temperature

limit control opens.