Setting the Unit

IMPORTANT NOTE:

Before hoisting and setting the unit in place, the short

piece of factory installed drain line located next to

the unit burner section must be removed from the

HX collector box drain valve to allow for passage of

the condensate drain line installed with the roof curb.

The condensate drain valve is located in the bottom

left corner of the heat exchanger collector box. See

Figure 25 (page 49)

. Remove the drain line and rubber

grommet located in the unit bottom pan, setting the

rubber grommet aside for later use.
• Set unit in place on curb as instructed in the Rigging

and Hoisting section of unit installation instructions.

IMPORTANT NOTE:

R8HE models may be lifted without the control access

panel in place to accommodate the passage and

installation of the condensate drain line.

WARNING:

To avoid accidental injury 6”x6” boards should

be placed across corners of the roof curb while

routing the condensate drain line up through

the bottom of the unit. After enough drain line

is passed through the bottom pan opening to

guide from inside the control / burner area the

boards may be removed for lowering the unit the

remainder of the way onto the curb.

• While lowering unit onto the curb, carefully pass the

first few inches of the 24 inch condensate drain line left

outside the top of the curb up through the hole in the

bottom pan below the collector box drain fitting.

• While holding the end of the drain line continue lowering

the unit until fully seated on curb ensuring the drain line

feeds up through the hole and does not become trapped

or kinked under the unit.

C o m p l e t i n g t h e H e a t E x c h a n g e r
Condensate Drain Installation

IMPORTANT NOTE

Downflow applications require the factory set

position of the condensate drain valve be changed

from the horizontal (H) to downflow (D) position. The

condensate drain valve is located in the bottom left

corner of the heat exchanger collector box to the left
of the inducer motor. See

Figure 25

. Carefully rotate

the valve 90 degrees in a clockwise direction until the

arrow is pointing vertically downward.
1. Slide the rubber grommet (large diameter first) down

the 24” of tubing and reinstall back into the unit bottom

pan ensuring a water tight seal. Additional sealing is

permissible.

2. Route the drain line up and onto to the condensate

drain valve barbed fitting. Cut hose to length required

to keep line from bending and secure to barbed fitting

using the spring hose lamp provided in the kit.

Condensate Disposal

• The method for disposing of condensate varies according

to local codes. Consult your local code or authority

having jurisdiction.

• Each of the condensate drain lines must be J-trapped

using field supplied parts. After the condensate lines

are J-trapped, they may be combined together into a

single run to the drain. The drain lines must be routed

downward to ensure proper drainage from furnace.

• Neutralizer kit P/N 902377 is available for use with this

furnace. Please follow the instructions provided with the

kit.

• For Installations where there is limited clearance for

the J-Trap (such as an attic where it may be installed

between ceiling joists), either side of the J-Trap can be
shortened to a minimum of 3 Inches. See

Figure 25

(page 49)

.

Completing the Vent Pipe Installation and
Assembly

1. Connect the horizontal 13.25” x 2” PVC pipe that came

supplied with the unit to the inducer motor rubber coupler

and secure using the 3” hose clamp provided.

2. Clean the opposite end of vent pipe and cement the 2”

x 22.5 degree elbow onto the 2” pipe at this time. Orient

elbow in a downward position.