Table 13. blower performance - 4 & 5 ton, And the rating, Table 13 – Reznor R8HE Unit Installation Manual User Manual

Page 32: For heating or, If the measured temperature rise, 208 volt operation

background image

32

R8HE -X48*096(X, XA) & R8HE -X60*096(X, XA)

96,000 BTUH, 38”-42” CABINET, 11”X10” BLOWER W- 1 HP ECM MOTOR

230 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1347

65

1295

68

1242

71

1187

74

1131

78

1077

82

1023

86

970

91

916

96

1

0

0

0

1402

63

1353

65

1305

67

1252

70

1199

73

1147

77

1094

80

1039

85

984

89

0

1

0

0

1457

60

1412

62

1367

64

1317

67

1267

69

1216

72

1165

76

1109

79

1052

84

1

1

0

0

1517

58

1468

60

1420

62

1374

64

1328

66

1279

69

1229

72

1172

75

1115

79

0

0

1

0

1576

56

1524

58

1472

60

1431

61

1389

63

1341

66

1293

68

1236

71

1178

75

1

0

1

0

1625

54

1576

56

1528

58

1485

59

1442

61

1394

63

1346

65

1289

68

1233

71

0

1

1

0

1674

53

1629

54

1583

56

1539

57

1494

59

1446

61

1398

63

1343

66

1287

68

1

1

1

0

1721

51

1675

53

1629

54

1583

56

1538

57

1491

59

1445

61

1390

63

1336

66

0

0

0

1

1768

50

1721

51

1674

53

1628

54

1582

56

1537

57

1491

59

1438

61

1384

64

1

0

0

1

1807

49

1762

50

1717

51

1671

53

1626

54

1580

56

1534

57

1483

59

1433

61

0

1

0

1 1846

48

1803

49

1759

50

1715

51

1670

53

1623

54

1576

56

1529

58

1482

59

1

1

0

1

1889

47

1843

48

1798

49

1754

50

1710

51

1663

53

1617

54

1571

56

1526

58

0

0

1

1

1931

46

1884

47

1837

48

1793

49

1749

50

1703

52

1657

53

1613

55

1569

56

1

0

1

1

1970

45

1925

46

1881

47

1836

48

1792

49

1747

50

1703

52

1658

53

1614

54

0

1

1

1

2008

44

1967

45

1910

46

1880

47

1834

48

1791

49

1748

50

1704

52

1659

53

1

1

1

1

2038

43

1980

44

1939

46

1910

46

1891

47

1874

47

1857

47

1809

49

1760

50

208 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1308

67

1252

70

1196

74

1139

77

1082

81

1025

86

967

91

915

96

863

102

1

0

0

0

1363

65

1309

67

1255

70

1199

73

1143

77

1088

81

1033

85

979

90

926

95

0

1

0

0

1417

62

1366

64

1314

67

1259

70

1203

73

1151

76

1098

80

1043

84

988

89

1

1

0

0

1470

60

1418

62

1366

64

1315

67

1265

70

1212

73

1159

76

1102

80

1045

84

0

0

1

0

1523

58

1471

60

1418

62

1372

64

1326

66

1273

69

1220

72

1161

76

1102

80

1

0

1

0

1566

56

1515

58

1464

60

1417

62

1371

64

1321

67

1271

69

1211

73

1151

76

0

1

1

0

1608

55

1559

56

1509

58

1462

60

1415

62

1369

64

1322

67

1261

70

1200

73

1

1

1

0

1650

53

1602

55

1554

57

1508

58

1461

60

1411

62

1362

65

1303

68

1245

71

0

0

0

1

1691

52

1645

53

1599

55

1553

57

1507

58

1454

60

1401

63

1345

65

1289

68

1

0

0

1

1737

51

1691

52

1644

54

1599

55

1554

57

1503

59

1451

61

1396

63

1342

66

0

1

0

1 1783

49

1736

51

1689

52

1645

53

1601

55

1551

57

1501

59

1448

61

1394

63

1

1

0

1

1823

48

1776

50

1730

51

1684

52

1638

54

1589

55

1539

57

1488

59

1437

61

0

0

1

1

1862

47

1817

48

1771

50

1723

51

1675

53

1626

54

1577

56

1529

58

1480

59

1

0

1

1

1904

46

1857

47

1810

49

1763

50

1717

51

1672

53

1627

54

1599

55

1572

56

0

1

1

1

1946

45

1898

46

1849

48

1804

49

1758

50

1717

51

1676

52

1670

53

1664

53

1

1

1

1

1977

44

1936

45

1895

46

1878

47

1860

47

1809

49

1757

50

1709

51

1660

53

NOTES:

* May be electrical code C, D, or K.

1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.

2. Temperature rises in tables are approximate. Actual temperature rises may vary.

3. Shaded areas are not recommended or approved for proper heating operation of equipment.

Heat rise: Btu/h (Input) = CFM * Δ T * 1.08

Δ T = (Btu/h * 0.95) / (CFM * 1.08)

Table 13. Blower Performance - 4 & 5 Ton