Vent termination, Warning, Horizontal ground mount – Reznor R8HE Unit Installation Manual User Manual

Page 6: Roof mounted unit (roof curb and roof not shown)

background image

6

WARNING:

Combustible air must not be drawn from a

contaminated atmosphere. Excessive exposure

to contaminated combustion air will result in

safety and performance related problems.

To maximize heat exchanger life, the combustion air

must be free of chemicals which form corrosive acidic

compounds in the combustion gases.

IMPORTANT NOTE:

Do not store any chemicals with flammable or caustic

vapors near the vent termination. Some examples of

these chemicals are:

• C

arbon

tetraChloride

• G

asoline

/K

erosene

• C

ements

,

Glues

,

paint

removers

,

varnishes

,

etC

.

• h

aloGen

type

refriGerants

• C

leaninG

solvents

• h

ydroChloriC

aCid

• C

hlorine

based

swimminG

pool

ChemiCals

• m

asonry

aCid

washinG

materials

• C

hlorinated

waxes

&

Cleaners

• p

ermanent

wave

solutions

• d

e

-

iCinG

salts

or

ChemiCals

• w

ater

softeninG

ChemiCals

Vent Termination

This unit has been developed for use with a combination

heat exchanger condensate drain and venting system

designed to operate only with this type of system.

Condensate Drain and Vent Kits are available for purchase

as accessory items.
Horizontal ground mount applications can use P/N-922323

to attach the 13.25” x 2” PVC pipe within the control area of

this unit. Rooftop mount applications can use the downflow

condensate drain / vent kit (P/N-922485).
If Nordyne kits are not being used, see Appendix on

page

43

or

page 45

for your specific application.

WARNING:

This unit is intended for outdoor installation

only. This unit must be vented to the outdoors.

No additional venting shall be used. Do not vent

the unit through a conventional venting system.

The vent and drain assembly must be installed to
assure proper operation of the unit.

Figure 2

shows the

proper installation of the vent and drain assembly for both

horizontal and downflow applications. The fasteners used

to secure the vent and drain assembly have been included

in the kit. The following list summarizes the requirements

for the location of the vent system termination:

• The location of the vent termination must be consistent

with the National Fuel Gas Code (ANSI Z223.1) or CAN/

CGA-B149 Installation Codes.

• The vent termination must be located at least 4 feet

horizontally from any electric meters, gas meters,

regulators, and relief equipment.

HORIZONTAL GROUND MOUNT

Combined condensate

Drain / Vent System

ROOF MOUNTED UNIT

(ROOF CURB AND ROOF NOT SHOWN)

2” PVC x 22.5 Degree Elbow

& 1/4” Mesh Screen

Figure 2. Heat Exchanger Condensate Drain

& Vent Assembly

• The vent termination must be located at least 3 feet

above any forced air inlet located within 10 feet.

• The vent termination must be located at least 4 feet

below, 4 feet horizontally from, or 1 foot above any

door, window, or gravity air inlet into any building.

• The unit should be installed in a way that prevents any

obstruction of the vent termination during accumulating

snow.

• Verify exhaust gases will not impinge on windows

or building surfaces, which may be compromised or

damaged by condensation.

• Do not install the unit such that exhaust from the vent

termination is directed into window wells, stairwells,

under decks, or in alcoves or similarly recessed areas.