GAS SUPPLY & PIPING

WARNING:

FIRE OR EXPLOSION HAZARD

• Failure to follow safety warnings exactly could

result in serious injury or property damage.

• Installation and service must be performed

by a qualified installer, service agency or the

gas supplier.

• Do not store or use gasoline or other flammable

vapors and liquids in the vicinity of this or any
other appliance.

WHAT TO DO IF YOU SMELL GAS

• Do not try to light any appliance.
• Do not touch any electrical switch; do not use

any phone in your building.

• Leave the building immediately.
• Immediately call your gas supplier from a

neighbor’s phone. Follow the gas supplier’s

instructions.

• If you cannot reach your gas supplier, call the

fire department.

AVERTISSEMENT:

RISQUE D’INCENDIE OU D’ EXPLOSION

• Le non-respect des avertissements de sécurité

pourrait entraîner des blessures graves, la

mort ou des dommages matériels.

• L’installation et l’entretien doivent être

effectués par un installateur qualifié, un

organisme de service ou le fournisseur de

gazstaller, service agency or the gas supplier.

• Ne pas entreposer ni utiliser de l’essence ni

d’autres vapeurs ou liquides inflammables

dans le voisinage de cet appareil, ni de tout

autre appareil.

QUE FAIRE S’IL Y A UNE ODEUR DE GAZ

• Ne pas tenter d’allumer aucun appareil.
• Ne toucher à aucun interrupteur électrique;

n’utiliser aucun téléphone dans le bâtiment.

• Évacuer l’immeuble immédiatement.
• Appeler immédiatement le fournisseur de

gaz en employant le téléphone d’un voisin.

Respecter à la lettre les instructions du

fournisseur de gaz.

• Si personne ne répond, appeler le service des

incendies.

• All gas piping must be installed in compliance with

local codes and utility regulations. In the absence

of local codes the gas line installation must comply

with the latest edition of the National Fuel Gas Code

ANSI Z223.1 or CAN/CGA B149 Installation Codes.

• Some local codes require the installation of a

manual main shut-off valve and ground joint union

external to the unit. The shut-off valve should be

readily accessible for service and/or emergency

use. Consult the local utility or gas supplier for

additional requirements regarding placement of
the manual main gas shut-off. See

Figure 6 (page

16)

.

• The manifold pressure must be set to the appropriate

value for your installation. To measure and adjust
the manifold pressure see

page 20

.

• Gas piping must never run in or through air ducts,

chimneys, gas vents, or elevator shafts.

• Compounds used to seal joints on gas piping must

be resistant to the actions of LP propane gas.

• The main gas shutoff valve and main power

disconnect to the unit must be properly labeled

by the installer in case emergency shutdown is

required.

• An 1/8 inch NPT plugged tap can be installed in the

gas line immediately upstream of the gas supply

connection to the unit for use when measuring

the gas supply pressure when not using the inlet

pressure tap supplied on the factory installed gas

valve. The plug should be readily accessible for

service use.

• A drip leg should be installed in the vertical pipe

run to the unit. See

Figure 6

.

This unit only has right side gas entry. When connecting

the gas, provide clearance between the gas supply line

and the entry hole in the unit’s casing to avoid unwanted

noise and/or damage to the unit. A typical gas service
hookup is shown in

Figure 6

.

Table 14 (page 33)

lists gas pipe capacities for standard

pipe sizes as a function of length in typical applications

based on nominal pressure drop in the line.

Leak Check

WARNING:

FIRE OR EXPLOSION HAZARD

Never test for gas leaks with an open flame. Check

all connections using a commercially available

soap solution. A fire or explosion may result

causing property damage, personal injury or

loss of life. Failure to follow the safety warnings

exactly could result in serious injury, death or

property damage.

After the gas piping to the unit is complete, all connections

must be tested for gas leaks. This includes pipe connections

at the main gas valve, emergency shutoff valve and

other gas connectors. A soap and water solution can be