beautypg.com

Cleaning of burners, Replacement parts troubleshooting, Cooling mode – Reznor R8HE Unit Installation Manual User Manual

Page 25: Heating mode, Caution, Replacement parts, Troubleshooting cooling mode

background image

25

Cleaning of Burners

If the burners must be cleaned, follow the steps below.

1. Shut off the gas supply to the unit either at the meter

or at a manual valve in the supply piping.

2. Turn off all power to the unit and set the thermostat to

the lowest temperature setting.

3. Remove the louvered control access panel from the

unit.

4. Turn the gas control switch to the OFF position. See

Figure 9 (page 34)

for gas valve shut off instructions.

5. Disconnect the wires from the gas valve, ignitor, and

flame sensor.

NOTE: Mark wires to prevent miswiring

of unit when reassembling.

CAUTION:

To prevent damage to the unit or internal

components, it is recommended that two

wrenches be used when loosening or tightening

nuts. Do not over tighten!

6. Using two wrenches, separate the ground-joint union

in the gas supply piping at the unit.

7. Remove the piping between the gas valve and the

ground-joint union (if applicable).

8. Remove all screws securing the burner assembly to

the unit.

9. Carefully remove the burner assembly from the unit.

DO NOT DAMAGE THE IGNITER WHILE REMOVING

THE BURNER ASSEMBLY.

10. Inspect the burners for accumulated dust or debris.

If necessary carefully clean them with a soft wire

brush and a vacuum cleaner.

DO NOT DAMAGE THE

IGNITER WHILE CLEANING THE BURNER.

11. Replace all the parts in reverse order from which they

were removed.

12. Follow the lighting instructions found on the lower unit

door to return the unit to operation.

13. Verify proper operation after servicing.

REPLACEMENT PARTS

Replacement parts are available through all Nordyne

distributors. Please have the complete model and serial

number of the unit when ordering replacement parts.

ELECTRICAL:

• Blower Control Board

• Ignitors/Flame Sensors

• Capacitors

• Pressure Switches

• Compressors

• Relays

• Contactors

• Temperature Limit Switches

• Gas Valves

• Thermostats

• Hall Effect Sensor

• Time Delay Relays

• Ignition Controls

• Transformers

MOTORS:

• Blower Motor
• Fan Motor
• Inducer Blower Motor

COMPONENTS:

• Blower Assembly

• Fan Grille

• Burner Manifold

• Filter/Driers

• Burners/Orifices

• Gaskets

• Cabinet Panels

• Heat Exchanger

• Expansion Valves

Table 5. Furnace Control Board Fault Conditions

DIAGNOSTIC DESCRIPTION

GREEN LED

RED LED

Control Fault (No Power)

Off

Off

L1/Neutral Polarity Fault

Flash

Flash

1 Hour Lockout

Alternating Flash

Normal Operation

On

On

Pressure Switch Closed Fault

On

Flash

Pressure Switch Open Fault

Flash

On

Open Limit Switch Fault

Flash

Off

Motor Fault

On

Off

Blocked Condensate Drain or Vent

OFF

Flash

DIAGNOSTIC DESCRIPTION

YELLOW LED

Low Flame Sensor Signal

Continuous Flash

Flame Present

On

DIAGNOSTIC

DESCRIPTION

GREEN

LED

RED

LED

VARIABLE

SPEED

FURNACES

Control Fault (No Power)

Off

Off

Normal Operation

On

On

Motor Fault

On

Flash

Communications Fault

Flash

Flash

Table 6. Motor Control Board Fault Conditions

TROUBLESHOOTING

Cooling Mode

If the unit does not operate in the cooling mode, check

the following:
• Verify the thermostat is operating properly

• Verify electrical power to the unit is turned on

• Verify the filters are not dirty

• Verify the service doors are in place

• Verify the 3 amp fuse is operational

• Verify the anti-short cycle timer’s 5 minute cycle has

finished.

• Verify the LED flash code (on the blower control board)

against the diagnostic codes listed in

Table 5

or on the

wiring diagrams:

Figure 13 (page 37)

,

Figure 14 (page

38)

, &

Figure 15 (page 39)

.

Heating Mode

If the unit does not operate in the heating mode, check

the following:
• Verify the thermostat is operating properly

• Verify electrical power to the unit is turned on

• Verify the filters are not dirty

• Verify the gas is turned on and the manual shut-off valve

is open and the gas valve switch is in the ON position

• Verify the service doors are in place

• Verify the flame roll-out switch is closed

• Verify the 3 amp fuse is operational

• Verify the LED flash codes on the furnace ignition control

board against the diagnostic codes listed in

Table 5

or

on the wiring diagrams:

Figure 13 (page 37)

,

Figure

14 (page 38)

, &

Figure 15 (page 39)

.

• Verify the LED flash codes on the motor control board

against the diagnostic codes listed in

Table 6

or on the

wiring diagrams:

Figure 13

,

Figure 14

, &

Figure 15

.