Table 12. Blower Performance - 3.5 Ton

R8HE / PPG3HE -X42K080XA

80,000 BTUH, 34” CABINET, 11”X10” BLOWER W- 1 HP ECM MOTOR

230 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1347

53

1295

55

1242

57

1187

60

1131

63

1077

66

1023

70

970

74

916

78

1

0

0

0

1402

51

1353

53

1305

55

1252

57

1199

59

1147

62

1094

65

1039

69

984

72

0

1

0

0

1457

49

1412

50

1367

52

1317

54

1267

56

1216

59

1165

61

1109

64

1052

68

1

1

0

0

1517

47

1468

49

1420

50

1374

52

1328

54

1279

56

1229

58

1172

61

1115

64

0

0

1

0

1576

45

1524

47

1472

48

1431

50

1389

51

1341

53

1293

55

1236

58

1178

61

1

0

1

0

1625

44

1576

45

1528

47

1485

48

1442

49

1394

51

1346

53

1289

55

1233

58

0

1

1

0 1674

43

1629

44

1583

45

1539

46

1494

48

1446

49

1398

51

1343

53

1287

55

1

1

1

0

1721

41

1675

43

1629

44

1583

45

1538

46

1491

48

1445

49

1390

51

1336

53

0

0

0

1

1768

40

1721

41

1674

43

1628

44

1582

45

1537

46

1491

48

1438

50

1384

52

1

0

0

1

1807

39

1762

40

1717

42

1671

43

1626

44

1580

45

1534

46

1483

48

1433

50

0

1

0

1

1846

39

1803

40

1759

41

1715

42

1670

43

1623

44

1576

45

1529

47

1482

48

1

1

0

1

1889

38

1843

39

1798

40

1754

41

1710

42

1663

43

1617

44

1571

45

1526

47

0

0

1

1

1931

37

1884

38

1837

39

1793

40

1749

41

1703

42

1657

43

1613

44

1569

45

1

0

1

1

1970

36

1925

37

1881

38

1836

39

1792

40

1747

41

1703

42

1658

43

1614

44

0

1

1

1

2008

36

1967

36

1925

37

1880

38

1834

39

1791

40

1748

41

1704

42

1659

43

1

1

1

1

2038

35

1998

36

1957

36

1924

37

1891

38

1874

38

1857

38

1809

39

1760

41

208 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1308

55

1252

57

1196

60

1139

63

1082

66

1025

70

967

74

915

78

863

83

1

0

0

0

1363

52

1309

54

1255

57

1199

59

1143

62

1088

66

1033

69

979

73

926

77

0

1

0

0

1417

50

1366

52

1314

54

1259

57

1203

59

1151

62

1098

65

1043

68

988

72

1

1

0

0

1470

49

1418

50

1366

52

1315

54

1265

56

1212

59

1159

62

1102

65

1045

68

0

0

1

0

1523

47

1471

48

1418

50

1372

52

1326

54

1273

56

1220

58

1161

61

1102

65

1

0

1

0

1566

46

1515

47

1464

49

1417

50

1371

52

1321

54

1271

56

1211

59

1151

62

0

1

1

0 1608

44

1559

46

1509

48

1462

49

1415

50

1369

52

1322

54

1261

57

1200

59

1

1

1

0

1650

43

1602

45

1554

46

1508

47

1461

49

1411

51

1362

52

1303

55

1245

57

0

0

0

1

1691

42

1645

43

1599

45

1553

46

1507

47

1454

49

1401

51

1345

53

1289

55

1

0

0

1

1737

41

1691

42

1644

43

1599

45

1554

46

1503

47

1451

49

1396

51

1342

53

0

1

0

1

1783

40

1736

41

1689

42

1645

43

1601

45

1551

46

1501

47

1448

49

1394

51

1

1

0

1

1823

39

1776

40

1730

41

1684

42

1638

44

1589

45

1539

46

1488

48

1437

50

0

0

1

1

1862

38

1817

39

1771

40

1723

41

1675

43

1626

44

1577

45

1529

47

1480

48

1

0

1

1

1904

37

1857

38

1810

39

1763

40

1717

42

1672

43

1627

44

1599

45

1572

45

0

1

1

1

1946

37

1898

38

1849

39

1804

40

1758

41

1717

42

1676

43

1670

43

1664

43

1

1

1

1

1977

36

1936

37

1895

38

1878

38

1860

38

1809

39

1757

41

1709

42

1660

43

NOTES:

* May be electrical code C, D, or K.

1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.

2. Temperature rises in tables are approximate. Actual temperature rises may vary.

3. Shaded areas are not recommended or approved for proper heating operation of equipment.

Heat rise: Btu/h (Input) = CFM * Δ T * 1.08

Δ T = (Btu/h * 0.95) / (CFM * 1.08)