Table 11. blower performance - 3 ton, Table 11, 208 volt operation – Reznor R8HE Unit Installation Manual User Manual
Page 30
30
R8HE / PPG3HE -X36*080(X, XA)
80,000 BTUH, 30” CABINET, 11”X8” BLOWER W- 1 HP ECM MOTOR
230 VOLT OPERATION
SWITCH
SETTINGS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1
2
3
4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
0
0
0
0
1272
55
1227
57
1181
60
1145
61
1108
64
1076
65
1043
67
1005
70
967
73
1
0
0
0
1323
53
1282
55
1241
57
1205
58
1170
60
1135
62
1101
64
1062
66
1024
69
0
1
0
0
1374
51
1338
53
1301
54
1266
56
1231
57
1195
59
1158
61
1119
63
1080
65
1
1
0
0
1424
49
1387
51
1350
52
1314
54
1279
55
1242
57
1205
58
1167
60
1130
62
0
0
1
0
1474
48
1437
49
1399
50
1363
52
1326
53
1289
55
1251
56
1215
58
1179
60
1
0
1
0
1516
46
1478
48
1441
49
1404
50
1366
52
1329
53
1292
54
1257
56
1222
58
0
1
1
0
1557
45
1520
46
1483
47
1445
49
1406
50
1370
51
1333
53
1299
54
1265
56
1
1
1
0 1598
44
1559
45
1521
46
1482
47
1444
49
1409
50
1374
51
1339
53
1304
54
0
0
0
1
1638
43
1598
44
1558
45
1520
46
1481
48
1448
49
1415
50
1379
51
1343
52
1
0
0
1
1674
42
1634
43
1595
44
1557
45
1520
46
1484
47
1448
49
1413
50
1379
51
0
1
0
1
1709
41
1671
42
1632
43
1595
44
1558
45
1519
46
1480
48
1448
49
1415
50
1
1
0
1
1741
40
1702
41
1664
42
1628
43
1593
44
1555
45
1517
46
1484
47
1452
48
0
0
1
1
1772
40
1734
41
1695
42
1662
42
1628
43
1591
44
1554
45
1521
46
1488
47
1
0
1
1 1809
39
1772
40
1735
41
1718
41
1701
41
1662
42
1623
43
1589
44
1555
45
0
1
1
1
1846
38
1811
39
1775
40
1774
40
1773
40
1732
41
1691
42
1657
42
1622
43
1
1
1
1
1928
36
1890
37
1852
38
1810
39
1767
40
1732
41
1697
41
1658
42
1618
43
208 VOLT OPERATION
SWITCH
SETTINGS
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
1
2
3
4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE
0
0
0
0
1218
58
1175
60
1132
62
1097
64
1062
66
1024
69
986
71
950
74
914
77
1
0
0
0
1270
55
1230
57
1191
59
1153
61
1116
63
1079
65
1043
67
1005
70
966
73
0
1
0
0
1321
53
1285
55
1249
56
1209
58
1169
60
1135
62
1100
64
1059
66
1018
69
1
1
0
0
1373
51
1335
53
1298
54
1260
56
1222
58
1185
59
1147
61
1107
64
1066
66
0
0
1
0
1425
49
1386
51
1346
52
1311
54
1275
55
1235
57
1194
59
1154
61
1114
63
1
0
1
0
1466
48
1426
49
1387
51
1350
52
1314
54
1274
55
1234
57
1195
59
1156
61
0
1
1
0
1507
47
1467
48
1427
49
1390
51
1352
52
1313
54
1273
55
1236
57
1198
59
1
1
1
0
1543
46
1504
47
1466
48
1425
49
1383
51
1347
52
1312
54
1274
55
1237
57
0
0
0
1
1578
45
1542
46
1505
47
1460
48
1414
50
1382
51
1350
52
1313
54
1276
55
1
0
0
1 1615
44
1575
45
1536
46
1494
47
1452
48
1417
50
1381
51
1346
52
1312
54
0
1
0
1
1651
43
1609
44
1567
45
1529
46
1490
47
1451
48
1412
50
1380
51
1347
52
1
1
0
1
1683
42
1642
43
1601
44
1564
45
1528
46
1490
47
1452
48
1416
50
1381
51
0
0
1
1
1715
41
1675
42
1634
43
1600
44
1565
45
1528
46
1491
47
1453
48
1414
50
1
0
1
1
1754
40
1731
41
1708
41
1670
42
1632
43
1593
44
1554
45
1515
46
1477
48
0
1
1
1
1792
39
1787
39
1782
39
1741
40
1699
41
1658
42
1617
44
1578
45
1539
46
1
1
1
1
1865
38
1824
39
1783
39
1741
40
1698
41
1658
42
1617
44
1579
45
1540
46
NOTES:
* May be electrical code C, D, or K.
1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.
2. Temperature rises in tables are approximate. Actual temperature rises may vary.
3. Shaded areas are not recommended or approved for proper heating operation of equipment.
Heat rise: Btu/h (Input) = CFM * Δ T * 1.08
Δ T = (Btu/h * 0.95) / (CFM * 1.08)
Table 11. Blower Performance - 3 Ton