beautypg.com

Table 11. blower performance - 3 ton, Table 11, 208 volt operation – Reznor R8HE Unit Installation Manual User Manual

Page 30

background image

30

R8HE / PPG3HE -X36*080(X, XA)

80,000 BTUH, 30” CABINET, 11”X8” BLOWER W- 1 HP ECM MOTOR

230 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1272

55

1227

57

1181

60

1145

61

1108

64

1076

65

1043

67

1005

70

967

73

1

0

0

0

1323

53

1282

55

1241

57

1205

58

1170

60

1135

62

1101

64

1062

66

1024

69

0

1

0

0

1374

51

1338

53

1301

54

1266

56

1231

57

1195

59

1158

61

1119

63

1080

65

1

1

0

0

1424

49

1387

51

1350

52

1314

54

1279

55

1242

57

1205

58

1167

60

1130

62

0

0

1

0

1474

48

1437

49

1399

50

1363

52

1326

53

1289

55

1251

56

1215

58

1179

60

1

0

1

0

1516

46

1478

48

1441

49

1404

50

1366

52

1329

53

1292

54

1257

56

1222

58

0

1

1

0

1557

45

1520

46

1483

47

1445

49

1406

50

1370

51

1333

53

1299

54

1265

56

1

1

1

0 1598

44

1559

45

1521

46

1482

47

1444

49

1409

50

1374

51

1339

53

1304

54

0

0

0

1

1638

43

1598

44

1558

45

1520

46

1481

48

1448

49

1415

50

1379

51

1343

52

1

0

0

1

1674

42

1634

43

1595

44

1557

45

1520

46

1484

47

1448

49

1413

50

1379

51

0

1

0

1

1709

41

1671

42

1632

43

1595

44

1558

45

1519

46

1480

48

1448

49

1415

50

1

1

0

1

1741

40

1702

41

1664

42

1628

43

1593

44

1555

45

1517

46

1484

47

1452

48

0

0

1

1

1772

40

1734

41

1695

42

1662

42

1628

43

1591

44

1554

45

1521

46

1488

47

1

0

1

1 1809

39

1772

40

1735

41

1718

41

1701

41

1662

42

1623

43

1589

44

1555

45

0

1

1

1

1846

38

1811

39

1775

40

1774

40

1773

40

1732

41

1691

42

1657

42

1622

43

1

1

1

1

1928

36

1890

37

1852

38

1810

39

1767

40

1732

41

1697

41

1658

42

1618

43

208 VOLT OPERATION

SWITCH

SETTINGS

0.20

0.30

0.40

0.50

0.60

0.70

0.80

0.90

1.00

1

2

3

4 CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE CFM RISE

0

0

0

0

1218

58

1175

60

1132

62

1097

64

1062

66

1024

69

986

71

950

74

914

77

1

0

0

0

1270

55

1230

57

1191

59

1153

61

1116

63

1079

65

1043

67

1005

70

966

73

0

1

0

0

1321

53

1285

55

1249

56

1209

58

1169

60

1135

62

1100

64

1059

66

1018

69

1

1

0

0

1373

51

1335

53

1298

54

1260

56

1222

58

1185

59

1147

61

1107

64

1066

66

0

0

1

0

1425

49

1386

51

1346

52

1311

54

1275

55

1235

57

1194

59

1154

61

1114

63

1

0

1

0

1466

48

1426

49

1387

51

1350

52

1314

54

1274

55

1234

57

1195

59

1156

61

0

1

1

0

1507

47

1467

48

1427

49

1390

51

1352

52

1313

54

1273

55

1236

57

1198

59

1

1

1

0

1543

46

1504

47

1466

48

1425

49

1383

51

1347

52

1312

54

1274

55

1237

57

0

0

0

1

1578

45

1542

46

1505

47

1460

48

1414

50

1382

51

1350

52

1313

54

1276

55

1

0

0

1 1615

44

1575

45

1536

46

1494

47

1452

48

1417

50

1381

51

1346

52

1312

54

0

1

0

1

1651

43

1609

44

1567

45

1529

46

1490

47

1451

48

1412

50

1380

51

1347

52

1

1

0

1

1683

42

1642

43

1601

44

1564

45

1528

46

1490

47

1452

48

1416

50

1381

51

0

0

1

1

1715

41

1675

42

1634

43

1600

44

1565

45

1528

46

1491

47

1453

48

1414

50

1

0

1

1

1754

40

1731

41

1708

41

1670

42

1632

43

1593

44

1554

45

1515

46

1477

48

0

1

1

1

1792

39

1787

39

1782

39

1741

40

1699

41

1658

42

1617

44

1578

45

1539

46

1

1

1

1

1865

38

1824

39

1783

39

1741

40

1698

41

1658

42

1617

44

1579

45

1540

46

NOTES:

* May be electrical code C, D, or K.

1. Factory settings are in bold. Use of any other switch setting may result in nuisance trips and should be verified for the application.

2. Temperature rises in tables are approximate. Actual temperature rises may vary.

3. Shaded areas are not recommended or approved for proper heating operation of equipment.

Heat rise: Btu/h (Input) = CFM * Δ T * 1.08

Δ T = (Btu/h * 0.95) / (CFM * 1.08)

Table 11. Blower Performance - 3 Ton