beautypg.com

About the kit, Before setting unit on the curb, Warning – Reznor R8HE Unit Installation Manual User Manual

Page 47: Important notice to installer

background image

47

APPENDIX B - HEAT EXCHANGER CONDENSATE DRAIN & VENT KIT

(ROOF CURB MOUNT APPLICATIONS)

WARNING:

ELECTRICAL SHOCK, FIRE OR

EXPLOSION HAZARD

Failure to follow safety warnings exactly could

result in serious injury or property damage.

Improper servicing could result in dangerous

operation, serious injury, death or property

damage.

• Before servicing, disconnect all electrical power

to the equipment.

• When servicing controls, label all wires prior

to disconnecting. Reconnect wires correctly.

• Verify proper operation after servicing.

About the Kit

This accessory kit is for use with 2-5 Ton 95% condensing

style package gas/electric unit roof curb mount installations

for proper heat exchanger condensate disposal and
venting.

Table 21

is a detailed listing of the components

in the drain and vent kit to allow the heat exchanger

condensate line to pass through the roof. Please check

the contents of the kit with that of the parts listing, and

familiarize yourself with each component.

Before Setting unit on the Curb

IMPORTANT NOTICE TO INSTALLER

When setting the roof curb for installation, routing

and securement of the gas heat exchanger

condensate drain line must be determined and

installed prior to setting the unit on the curb.

• Nordyne Condensate Drain & Vent Kit # 922485 is set

up for installing the HX condensate drain line straight

down through the roof. It is recommended to drill a

1.00”-1.25” diameter hole through the roof below the

rectangular opening located in outer close off curb panel

(G) of Nordyne offered curbs, approximately 15” in from

the short side of curb and 1”-2” in from the long side of
curb. See

Figure 24

.

• If drilling a hole is not an option, routing the condensate

drain hose over to the duct passage opening with enough

slope is acceptable as long as drain line is secured

to curb and duct, ensuring no kinks or traps can form

between the collector box drain or interior of the building.

Leave a minimum of 24” drain line extending out the

top of roof curb front close off panel (G) for passage

through unit bottom and connection to unit drain when
unit is being set. See

Figure 24

. Seal roof penetration

as required.

• It is recommended no non-serviceable connections are

introduced in the drain line between unit drain connection

and an accessible area within the building interior.

Securement of the drain line to the inside surface of

the roof curb is acceptable and should be made in the

wood nailer area (top 3.5”) to avoid possible leaks or

penetrations to roofing materials.

• Cut and remove the insulation covering the 2” x 3”

condensate drain passage in outer panel (G) only.

Before installing inner panel (G) make sure there is

enough slope and there are no kinks or high spots

that could trap water in the line prior to entering the

warmer interior of the building where a drain trap

is REQUIRED.

KIT SUPPLIED PARTS

DESCRIPTION

QTY

2” pvC

x

22.5 d

eGree

e

lbow

& 1/4” m

esh

s

Creen

1

s

prinG

h

ose

C

lamp

1

1/2” id

x

84” d

rain

h

ose

1

h

ose

C

lamp

3/4” d

iameter

1

s

elf

t

appinG

s

Crews

1

FIELD SUPPLIED PARTS

• PVC Solvent Cleaner and Pipe Cement.

• Additional condensate drain components to complete the

installation: PVC Pipe, Hose Clamps, Hangers.

Table 21. Kit and Field Supplied Parts

24” MINIMUM OF 1/2” I.D. TUBING

REQUIRED OUTSIDE OF ROOF

CURB TOP (R8HE MODELS ONLY)

1” - 2”

15”

1” to 1.25” Dia.
Through Roof

(G)

Figure 24. Roof Curb for 2 - 5 Ton Units