22

not close within 12 seconds, the control will display a

Pressure Switch Open with Inducer On Fault. If the hall

effect sensor switch does not close before 60 seconds

expires, the control will de-energize the inducer for 5

minutes and continue to display a Pressure Switch Open

with Inducer On Fault during the 5 minute inducer off

period. After the inducer has been off for 5 minutes, the

control energizes the inducer motor and restarts the 60

second pressure switch proving period.

5. Pre-Purge - If the hall effect sensor switch closes the

control runs the inducer on high speed for a 30 second

pre-purge time while monitoring the thermostat call for

heat, limit switch circuit, vent pressure switch, and flame

sense.

6. Igniter Warm Up - When the 30 second pre-purge time

has elapsed, the control begins the Hot Surface Ignition

(HSI) warm-up as follows:

Initial Power up: After 30 seconds of igniter warm-up, the

gas valve will open. The igniter circuit will stay energized

for 3 seconds after the gas valve opens.

After Initial Power up: The control has a programmed

adaptive ignition feature which varies the warm-up

period as follows: If ignition is successful the warm-up

is reduced by 3 seconds on each subsequent call for

heat until ignition failure occurs. Upon ignition failure,

the warm -up is increased by 3 seconds on the next try.

If successful, the timing remains fixed at this level. In

general, whenever ignition failure occurs the warm-up

interval is increased by 3 seconds on the next try.

If successful, it remains there. Minimum and maximum

warm-up time limits are set at 9 and 54 seconds.

7. Flame Proving / Ignition / Low Heat Operation - The

furnace control must prove flame via the flame sensor

5 seconds after the high main gas valve is energized.

• If flame is sensed, burners are on and the igniter cools

off. The Yellow LED will be lit.

• If no flame is sensed, the gas valve closes immediately

and the inducer continues to run on high. A second

trial for ignition (step 6) begins. If no flame is sensed

on the fifth try for ignition, the furnace control is locked

and the control will display 1 Hour Lockout Fault. The

thermostat must be opened for at least 10 seconds to

reset the furnace control after a lock out. Otherwise,

the furnace will attempt another ignition sequence

in 1 hour.

Low Fire Heat (Stage 1): If flame is present at the end

of the trial for ignition time, the control leaves High main

gas valve energized and inducer motor on High speed

for the first 15 seconds, and begins the heat blower

22 second on delay. Control inputs are continuously

monitored while the call for heat remains. The control

will always energize the gas valve on High fire with the

inducer on High speed for the first 15 seconds of any

heating cycle. After this 15 second period, the control

switches the gas valve to Low fire and inducer to Low

speed if no second stage (

W2) demand is present.

8. Blower Start-Up - After flame is proven, the furnace

control energizes the circulating air blower after 22

seconds. The blower will then ramp up to the airflow

selected for heating.

9. High Heat Staging (with 2 Stage Heat Thermostat) - Unit

will always start in High heat operation. See step 7 for

start up sequence. After the initial 15 second start up

sequence is satisfied, the control will move to Low heat

and wait for a

W2 call from a 2-stage thermostat. After a

second stage heat demand is present (

W2 energized),

the gas valve will open to High heat mode increasing

the flow of gas to the burners while the inducer and

blower motor ramp to high speed.

Single Stage Heat Thermostat with Automatic Heat

Staging - Automatic heat staging allows the unit to

operate as a two stage gas furnace with the use of a

single stage heating thermostat. With the ignition control

AUTO HEAT STAGE jumper repositioned from the OFF
position to the ON position, see

Figure 12 (page 36)

,

the gas furnace will automatically switch to High heat

mode of operation after a 10 minute delay. The induced

draft motor and blower motor will both ramp to high

speed.

10. When the thermostat has been satisfied, gas valve is

de-energized.

11. The inducer motor is de-energized after a 30 second

post purge.

12. The circulating air blower will remain energized for

approximately 120 seconds (factory setting) after the

demand for heat is no longer present.

13. Abnormal Conditions - If a limit switch opens during

heating operation the gas valve is de-energized

immediately. The control de-energizes the induced draft

motor and runs the indoor blower motor continuously

while the limit switch is open.

NOTE: This unit has two special features

programmed into the furnace control board for

safety and proper unit operation.

Thaw Cycle Start Up / Shutdown

The vent pressure switch is constantly monitored

throughout the ignition cycle. If after 1 minute of burner

ignition the vent pressure switch remains open, the

control will de-energize the gas valve, energize the main

blower, and begin another ignition sequence after a 30

second inter-purge. If after 5 cycles the pressure switch

fails to close the unit will lockout for a period of one hour.

The blower stays energized for the selected blower off

delay period. This feature only activates if the unit is off

for extended periods of time between heating cycles in

extremely cold weather which could lead to ice formation

over the vent pressure tap or the switch itself is faulty.

Any ice formation will clear after one or two trials. One

hour lockout period can be terminated by shutting off the

thermostat for 5-10 seconds or main power to unit for

1-2 seconds.