beautypg.com

Heat anticipator, Cooling configurations, Heating configurations – Reznor R8HE Unit Installation Manual User Manual

Page 13: Blower speed, Configuring the fixed speed blower, Selecting cooling airflow, Selecting heating airflow

background image

13

Heat Anticipator

Verify if the thermostat being used for the installation

has a heat anticipator setting. This function allows the

thermostat to anticipate the space heating rate and time

the burner to shutoff accordingly. Always refer to the

thermostat manufacturer’s instructions for correct settings.

• Add the current draw of the system heating components.

OR

• Measure the current flow on the thermostat

R-W circuit

after the circulating blower motor has started. Set the heat

anticipator according to the thermostat manufacturer’s

instructions for heat anticipator settings.

Cooling Configurations

This unit is designed to connect with any single stage

cooling thermostat. The connection between

Y1 on the

thermostat and

Y1 on the unit terminal strip energizes

cooling operation. See

Figure 10 (page 36)

.

Heating Configurations

This gas pack is factory configured for two stage gas

heating operation with a two stage heating thermostat.

Connect the low voltage thermostat White & Brown wires

to

W1 & W2, between the unit low voltage terminal board

and thermostat sub-base. See

Figure 10

.

To operate with a single stage heat thermostat, only

connect the low voltage thermostat White wire between

W1 on the unit low voltage terminal board and thermostat

sub-base. Reposition the automatic heat staging jumper

located on the ignition control module from OFF to ON

to set a 10 minute time delay before the gas furnace will

automatically move to high heat operation.

NOTE: When

low fire on the gas valve is energized, the furnace operates

in low fire mode at a lower blower speed and the timer

begins its delay function. If the room thermostat is not

satisfied before the timer activates, the furnace will stage

to high fire. The inducer motor and blower will ramp to a

higher speed until the thermostat is satisfied.

Blower Speed

The blower speed is preset at the factory for proper

fan only, heating, and cooling operation. These factory
settings are listed in

Table 8 (page 28)

,

Table 9 (page

28)

,

Table 10 (page 29)

,

Table 11 (page 30)

,

Table

12 (page 31)

&

Table 13 (page 32)

. For optimum

system performance and comfort, it may be necessary to

change the factory set speed.

To avoid personal injury

or property damage, make sure the motor leads do

not come into contact with any un-insulated metal

components of the unit.

NOTES:

• The CFM values listed in

Table 8

,

Table 9

,

Table 10

,

Table 11

,

Table 12

&

Table 13

are DEPENDANT on

duct static pressure for individual switch settings.

• If coil icing occurs, the basic cooling airflow selected

may be too low. Verify the selected setting is within
the range shown in

Table 8

and the system is properly

charged. If icing continues, raise the selected airflow

to the next higher tap.

• For maximum dehumidification and energy efficiency,

select an airflow near the middle or bottom of the CFM

range for that nominal capacity.

• The 2-stage heating feature of the unit requires

modulating the airflow. The unit will automatically adjust

the airflow to the appropriate rate when the unit heating

capacity changes.

Configuring the Fixed Speed Blower

The fixed speed blower assembly has been designed to

give the installer maximum flexibility for optimizing system

performance, efficiency, and comfort. It is equipped with

a microprocessor-controlled motor when coupled with a

fixed speed motor control board delivers constant torque

to optimize airflow in a variety of conditions and system

configurations. Because the blower can be configured in

many ways, it is important to read and follow all instructions

carefully.
Upon initial start up, the fixed speed blower must be

checked so that the factory settings match the unit with

the system, climatic conditions, and other system options.

With the blower installed and configured properly, the

furnace will change speed in response to changes in

system variables such as Heat/Cool setting, Fan Auto/

On, or 2 Stage furnace High/Low Heat. The fixed speed

blower is configured by setting the 8 switches for heating

and cooling operation located on the blower control board.

Use pins 1 to 4 to set the blower speed for heating and

pins 5 to 8 to set the speed for cooling. To determine the
appropriate switch settings for your installation, see

Table

9

,

Table 10

,

Table 11

,

Table 12

&

Table 13

for heating or

Table 8 for cooling. See

Figure 10 (page 36)

for switch

locations.

NOTE: For change in blower speed selection to

take effect, system power must be cycled off then restored

after 10 seconds.

Selecting Cooling Airflow
(Switches # 5, 6, 7, & 8)

The COOLING airflow is selected by setting switches # 5,
6, 7, & 8 on the motor control board (

Figure 10

).

Table 8

(page 28)

lists the recommended airflow values (CFM)

and switch settings for each nominal cooling system

capacity. All airflows for other modes of operation are

determined by these basic settings. For maximum capacity,

generally, a selection near the middle or top of the CFM

range for that nominal capacity is used. Factory settings

are displayed in BOLD ITALICS

Selecting Heating Airflow
(Switches # 1, 2, 3, & 4)

The HEATING airflow is selected by setting switches #

1, 2, 3, & 4 on the motor control board (Figure 10, Page
31).

Table 9

,

Table 10

,

Table 11

,

Table 12

&

Table 13

list the recommended airflow values (CFM) and switch

settings for each heat exchanger capacity. All airflows are

determined by these basic settings. For most applications

the factory heat setting will operate at a nominal rise based

on the furnace’s nominal efficiency and firing input. Follow

across the table row to find the switch setting and nominal