Form I-RPB, P/N 131782 R12, Page 7

*Optional

Downturn

Plenum

Furnace

Blower

Cabinet

Curb

Cap

1-7/8”

(48mm)

Roof

Curb

16”(406mm)

1-7/8”

(48mm)

AC

D

Return

Duct

Supply

Duct

1-7/8”(48mm)

1-1/2”

(38mm)

Lift Holes

(4 corners)

B

IMPORTANT: Top surface of curb MUST be sealed.

See instructions.

* Illustration is shown with an Option AQ5

or AQ8 downturn plenum. The system

can have a variety of configurations

which affect installation.

• If the system does not have a

downturn plenum, the discharge is

horizontal.

• Downturn plenum

Options AQ5 and

AQ8 are factory installed to be lifted

to the roof and set on the roof curb

as part of the packaged system.

FIGURE 3A - Optional

Roof Curb

IMPORTANT: Area enclosed by the roof curb must comply

with clearance to combustible materials. If roof is constructed

of combustible materials, area within curb must be either ven-

tilated, left open, or covered with non-combustible material

which has an "R" value of at least 5.0. If area within curb is

left open, higher radiated sound levels may result.

Roof Curb Dimensions (mm)

Size

125

150, 175 200, 225 250, 300

350

400

Option CJ1 - Roof Curb for (H)RPB

A

60-5/8

60-5/8

60-5/8

60-5/8

60-5/8

60-5/8

B

24-5/16

29-13/16 35-5/16 43-9/16

49-1/16

54-1/2

C** 56-15/16 56-15/16 56-15/16 56-15/16 56-15/16 56-15/16

D**

20-9/16

26-1/16

31-9/16 39-13/16 45-5/16 50-13/16

Option CJ2 - Roof Curb with Factory-Installed Downturn Plenum

Option AQ5 or AQ8

A

84-9/16

84-9/16

84-9/16 84-9/16

84-9/16

84-9/16

B

24-5/16

29-13/16 35-5/16 43-9/16

49-1/16

54-1/2

Size

125

150, 175 200, 225 250, 300

350

400

C** 80-13/16 80-13/16 80-13/16 80-13/16 80-13/16 80-13/16

D**

20-9/16

26-1/16

31-9/16 39-13/16 45-5/16 50-13/16

E

25-7/8

31-3/8

36-7/8

45-1/8

50-5/8

56-1/8

F

99-5/32 104-21/32 110-5/32 118-7/16 123-15/16 129-7/16

Size 125 150, 175 200, 225 250, 300 350 400

Option CJ1 - Roof Curb for (H)RPB

A

1540

1540

1540

1540

1540 1540

B

618

757

897

1106

1246 1384

C** 1446

1446

1446

1446

1446 1446

D**

522

662

802

1011

1151 1291

Option CJ2 - Roof Curb with Factory-Installed

Downturn Plenum Option AQ5 or AQ8

A

2148

2148

2148

2148

2148 2148

B

618

757

897

1106

1246 1384

Size 125 150, 175 200, 225 250, 300 350 400

C** 2053

2053

2053

2053

2053 2053

D**

522

662

802

1011

1151 1291

Roof Curb Dimensions (inches)

** C and D are roof opening dimensions.

Roof Curb Assembly

and Installation

Instructions

(FIGURES 3A and 3B)

Curbs are shipped unassembled. Field assembly and mounting on the roof are the

responsibility of the installer. All required hardware necessary to complete the assem-

bly is supplied.
Before installing roof curb, verify that the size is correct for the system being

installed.

1. Position curb cross rails and curb side rails as illustrated in FIGURE 3A. Join the

corners as illustrated in the corner detail (

FIGURE 3B).

2. Check the assembly for squareness. Adjust the roof curb so that the diagonal

measurements are equal within a tolerance of ± 1/8" (3mm).

3. Level the roof curb. To ensure a good weather tight seal between the curb cap and

the roof curb, the roof curb must be leveled in both directions with no twist end to

end. Shim level as required and secure curb to roof deck before proceeding with

flashing.

4. Install field-supplied flashing.

5. Before placing the unit into position, apply furnished 1/4" x 1-1/4" foam sealant

tape to top surface of curb, making good butt joint at corners. The unit must be

sealed to the curb to prevent water leakage into the curb area due to blown rain

and capillary action.

in this section apply to all curbs. See

FIGURES 3A and 3B and the curb installation

instructions below.