beautypg.com

3 burners and carryover system, 4 burner air adjustment, 0 check installation and startup – Reznor RPB Unit Installation Manual User Manual

Page 34: 1 check the installation prior to startup, 0 controls (cont'd), 2 pilot and ignition systems (cont'd)

background image

Form I-RPB, P/N 131782 R11, Page 34

NOTE: When checking for spark with the pilot burner assembly removed from the

burner rack, the pilot assembly must be grounded to the heater for proper spark.

If the above conditions are normal and no spark occurs, replace the ignition controller.

If the main gas valve fails to open with a normal full size pilot flame established, check

for the following:

a) Voltage between black and brown leads on the main gas valve is 20 to 32 VAC

and there is no main gas flow with the built-in manual valve in FULL OPEN

position -- the main valve is defective.

b) No voltage between black and brown leads on the main gas valve -- check for

disconnected or shorted flame sensor lead or flame sensor probe.

When the above conditions are normal and the main gas flow is still off, the ignition

controller is probably defective.

8.3 Burners and

Carryover

System

These duct furnaces have individually formed steel burners with accurately die-formed

ports to give controlled flame stability without lifting or flashback with either natural or

propane gas. The burners are lightweight and factory mounted in an assembly which

permits them to be removed as a unit for inspection or service.
Natural gas burner racks (except when equipped with electronic modulation Option

AG39 or AG40; see Paragraph 8.1.4) are equipped with two flash carryovers. Propane

gas burners are equipped with one flash carryover and a regulated gas lighter tube

system.

During regular service, check the main burner ports, the carryover assemblies, and the

orifices for cleanliness.

8.4 Burner Air

Adjustment

Burner air shutters are not normally required on natural gas furnaces. Air shutters are

required on propane gas units and may require adjustment.
Before making any adjustments to the air shutters, allow the heater to operate for

about fifteen minutes with the air shutters open. The slotted screw on the end manifold

bracket moves the air shutters and adjusts all burners simultaneously. Turning the

screw clockwise opens the shutters; counterclockwise closes the shutters. After the

furnace has been in operation for 15 minutes, close the air shutters observing the flame

for yellow-tipping. Open the shutters until the yellow disappears. A limited amount of

yellow-tipping is permissible for liquefied petroleum gases. Natural gas should not dis-

play any yellow-tipping.
When making the adjustment, close the air shutters no more than is necessary to elimi-

nate the problem condition.

DANGER

Failure to install and/or adjust air shutters according to directions

could cause property damage, personal injury, and or death.

9.0 Check

Installation and

Startup

9.1 Check the installation prior to startup:

Be certain the electrical supply matches voltage rating of the furnace. (Refer to the

rating plate.)

Check all field wiring against the wiring diagram. Be sure that wire gauges are as

required for the electrical load.

Be certain that the electrical entrances are sealed against the weather.

Check that fuses or circuit breakers are in place and sized correctly.

Verify that the condensate drain holes in the corners of the cabinet are open.

Check clearances from combustibles. Requirements are shown in Paragraph 4.2.

Check piping for leaks and proper gas line pressure. Bleed gas lines of trapped air.

See Paragraph 6.1.

a) Turn manual shutoff valve to off position.

b) Turn gas supply on.

c) Observe gas meter for movement, or

d) Attach pressure gauge readable to .1" w.c. and after turning gas on for ten

seconds, turn gas supply off. No change in pressure should occur over a three-

minute period.

8.0 Controls

(cont'd)

8.2 Pilot and

Ignition

Systems

(cont'd)